How battery capacity varies with discharge rate — essential for lead-acid sizing.
Updated Apr 19, 20262 min read
Formulas
Basic form
C_p = I^k · t
Runtime
t = H · (C / (I · H))^k (C = rated Ah at the H-hour rate, I in amps)
Peukert exponent k
1.1 – 1.25 for flooded lead-acid; ~1.05 AGM; ~1.05 Li-ion
Typical k values
Chemistry
k
Lead-acid (flooded)
1.20 – 1.30
Lead-acid (AGM)
1.05 – 1.15
Lead-acid (gel)
1.10 – 1.20
NiMH
1.05 – 1.10
Li-ion / LiFePO₄
~1.05
Example (100 Ah AGM, k=1.1)
Discharge rate
Available capacity
C/20 (5 A, rated)
100 Ah
C/10 (10 A)
~93 Ah
C/5 (20 A)
~87 Ah
C/2 (50 A)
~79 Ah
1C (100 A)
~74 Ah
Worked example: runtime at a heavy load
A 100 Ah flooded lead-acid battery is rated at the 20 hour rate (H = 20 h, so 5 A) and has k = 1.2. Drawing 25 A, the Peukert runtime is t = H × (C / (I × H))k = 20 × (100 / (25 × 20))1.2 = 20 × 0.21.2 = 20 × 0.145 = 2.90 hours. The capacity actually delivered is 25 A × 2.90 h = 72.5 Ah, about 27% less than the 100 Ah on the label, and well short of the naive 100 / 25 = 4 hours. A lithium battery with k = 1.05 under the same load gives 20 × 0.21.05 = 3.69 hours.
Finding k from two points: if a datasheet shows a battery lasting 20 h at 5 A and 5 h at 16 A, then k = ln(t1/t2) / ln(I2/I1) = ln(20 / 5) / ln(16 / 5) = 1.386 / 1.163 = 1.19. Two measured discharge times at different currents are enough, and the further apart the currents the better the estimate.
Limits of the law
It is an empirical fit, accurate across the range of currents it was fitted to (typically C/20 to about 1C) and unreliable well outside it. At very low current self-discharge dominates, and at very high current the internal resistance makes the fit fail.
It assumes constant current and temperature. Cold batteries lose more capacity than the law predicts, and variable loads need an averaging or step-by-step calculation.
It describes usable capacity, not total energy. Capacity not delivered at a high rate is partly recoverable after a rest, as the battery recovers voltage once the load drops.
Use the label rate. A battery rated at 100 Ah at the 10 hour rate and one rated at the 20 hour rate are not comparable; convert both to the same rate before choosing.
Combine with depth of discharge. For a lead-acid battery that should only be discharged to 50%, take half of the Peukert capacity as the usable amount.
Notes
Manufacturer capacity is specified at a reference discharge rate (often C/20 for lead-acid, C/5 for NiMH, 0.5C for Li-ion).
Peukert matters most for engine-start (high I) vs house loads (low I) comparisons.
Low-k chemistries (Li-ion) are robust to discharge rate — one reason Li-ion dominates modern portable.
Was this article helpful?
Cookies & ads
Tools run client-side — your inputs stay in your browser. No ad network is installed, so no ad cookies are set. Choose what this site may store on your device. Privacy · Cookies
Essential StorageTheme, consent state, CSRF tokens. Required for the site to work.
Always on
PersonalizationRecently used tools, custom colors, accessibility preferences. Stored locally on your device.
AdvertisingOnly applies if an ad network is installed. None is today, so no ad cookies are set either way. Details.
AnalyticsAggregate, anonymous page-view counts so we know which tools to improve.
AI IntegrationStores your API key locally for optional AI features. Key never leaves your device.