Under NEC Table 310.16, 14 AWG copper is rated 15 A (60 °C insulation), 20 A (75 °C) and 25 A (90 °C); 12 AWG is 20/25/30 A and 10 AWG 30/35/40 A. Those figures assume no more than three current-carrying conductors in a raceway, cable or earth and an ambient of 30 °C (86 °F). The NEC small-conductor rule (240.4(D)) then caps the fuse or breaker at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper, and terminal temperature ratings usually hold small wires to the 60 °C column. The table below is the copper and aluminum ampacity chart Cerrowire publishes from the 2017 NEC. It is a reference, not a design: the NEC edition your jurisdiction has adopted, local amendments and the equipment ratings govern, and a licensed electrician or engineer should size permanent wiring. To apply temperature and bundling factors, use the AWG Current Capacity Calculator.
Ampacity by wire size (NEC Table 310.16)
| Size (AWG or kcmil) | Copper 60 °C (A) | Copper 75 °C (A) | Copper 90 °C (A) | Aluminum 75 °C (A) | Aluminum 90 °C (A) |
|---|---|---|---|---|---|
| 14 | 15 | 20 | 25 | not listed | not listed |
| 12 | 20 | 25 | 30 | 20 | 25 |
| 10 | 30 | 35 | 40 | 30 | 35 |
| 8 | 40 | 50 | 55 | 40 | 45 |
| 6 | 55 | 65 | 75 | 50 | 55 |
| 4 | 70 | 85 | 95 | 65 | 75 |
| 3 | 85 | 100 | 115 | 75 | 85 |
| 2 | 95 | 115 | 130 | 90 | 100 |
| 1 | not listed | 130 | 145 | 100 | 115 |
| 1/0 | not listed | 150 | 170 | 120 | 135 |
| 2/0 | not listed | 175 | 195 | 135 | 150 |
| 3/0 | not listed | 200 | 225 | 155 | 175 |
| 4/0 | not listed | 230 | 260 | 180 | 205 |
| 250 kcmil | not listed | 255 | 290 | 205 | 230 |
| 300 kcmil | not listed | 285 | 320 | 230 | 260 |
| 350 kcmil | not listed | 310 | 350 | 250 | 280 |
| 500 kcmil | not listed | 380 | 430 | 310 | 350 |
| 600 kcmil | not listed | 420 | 475 | 340 | 385 |
| 750 kcmil | not listed | 475 | 535 | 385 | 435 |
| 1000 kcmil | not listed | 545 | 615 | 445 | 500 |
Insulation types in each column
| 60 °C (140 °F) | NM-B, UF-B (copper). Cerrowire lists no 60 °C ampacity for sizes above 2 AWG and no 60 °C aluminum column. |
|---|---|
| 75 °C (167 °F) | THW, THWN, SE, USE, XHHW (copper and aluminum). |
| 90 °C (194 °F) | THWN-2, THHN, XHHW-2, USE-2 (copper); XHHW-2, THHN, THWN-2 (aluminum). |
| Not listed | 14 AWG aluminum has no ampacity in the chart; 1 AWG and larger copper have no 60 °C value. |
Conditions behind the numbers
| Ambient | 30 °C (86 °F). Above that, multiply by the temperature correction factor of NEC Table 310.15(B)(2)(a) (2017 numbering; later editions renumbered it). Below 78 °F (about 26 °C) a correction is permitted. |
|---|---|
| Conductors | No more than three current-carrying conductors. With more, apply the adjustment factors of NEC Table 310.15(B)(3)(a) (2017 numbering): 80 % for 4 to 6, down to 35 % for 41 or more. Equipment grounding conductors are not counted; spare conductors that will be energized later are. |
| Terminals | NEC 110.14(C)(1): equipment for 14 AWG to 1 AWG conductors is assumed to be rated 60 °C, and for 1/0 and larger 75 °C, unless the equipment is marked otherwise. 600 V panelboards are typically limited to 75 °C. |
| Cable type | NM-B and UF-B cable is limited to 60 °C ampacity; SER, SEU and MC cable to 75 °C (Cerrowire calculator notes). |
| Final value | The smallest of: the corrected and adjusted ampacity, the terminal temperature limit and the cable-type limit. |
| Small conductors | NEC 240.4(D): overcurrent protection for copper no more than 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG, whatever the column says (the same ratings Cerrowire gives for copper NM, TW and UF wire). |
Worked examples
- 20 A branch circuit in 12/2 NM-B: NM-B is limited to the 60 °C column, so 20 A. The breaker may be 20 A.
- 12 AWG THHN in conduit, 6 current-carrying conductors: start from the 90 °C value, 30 A; × 0.80 for 4–6 conductors = 24 A. The 60 °C terminal limit (20 A) and the 240.4(D) cap (20 A) are lower, so the circuit is still 20 A.
- Service feeder, 4/0 aluminum XHHW-2 vs 2/0 copper THHN at 75 °C terminals: 180 A and 175 A respectively. Both can carry a 175 A load.
- Long runs: ampacity says nothing about voltage drop. A wire that is thermally fine can still lose too many volts over 100 ft or more; check with the Voltage Drop Calculator and the resistances in the Wire Gauge Table.
What this table does not cover
- Single insulated conductors in free air, high-voltage cable and high-temperature insulation are covered by other NEC tables, which are not reproduced here.
- Low-voltage DC wiring in vehicles and boats follows other rules (SAE, ABYC); see Automotive Wiring & Wire Gauge.
- Chassis-wiring or "power transmission" ampacity figures that circulate online are not from the NEC and are not given here.
- Earlier versions of this page listed "chassis" and "transmission" amps and a "60 °C ambient" note with no source; they have been removed.
Sources
- NFPA 70, National Electrical Code: Table 310.16 (numbered 310.15(B)(16) in the 2017 edition), 110.14(C)(1) and 240.4(D). The NEC is not freely downloadable, so the values come from a wire maker's published reproduction below. All Cerrowire pages were read on 6 October 2026.
- Cerrowire, Ampacity Charts (Wire Size & Amp Ratings), PDF Cerrowire_Ampacity_Chart_210405, 2021 (based on the 2017 NEC) (www.cerrowire.com/products/resources/tables-calculators/ampacity-charts/). Used for: Copper 60/75/90 C and aluminum 75/90 C ampacities and the insulation types for each column.
- Cerrowire, Ampacity Calculator (explanatory text), accessed 2026-10-06 (www.cerrowire.com/products/resources/tables-calculators/ampacity-calculator/). Used for: 30 C (86 F) ambient basis, three-conductor basis, 80 % to 35 % adjustment range, 110.14(C)(1) termination defaults, NM-B/UF-B 60 C limit.
- Cerrowire, Applications Charts (Size & AMP Ratings), accessed 2026-10-06 (www.cerrowire.com/products/resources/tables-calculators/applications-charts/). Used for: 14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A for copper NM, TW and UF wire.
Frequently asked questions
How many amps can 12 gauge wire carry?
Under NEC Table 310.16, 12 AWG copper is rated 20 A in the 60 °C column, 25 A at 75 °C and 30 A at 90 °C (≤ 3 current-carrying conductors, 30 °C ambient). But the NEC small-conductor rule, 240.4(D), limits the fuse or breaker protecting 12 AWG copper to 20 A, so in practice 12 AWG copper is a 20 A circuit. Your local code and the equipment's terminal rating govern.
What size wire for a 30 amp circuit?
10 AWG copper: it is rated 30 A at 60 °C, 35 A at 75 °C and 40 A at 90 °C, and the small-conductor rule caps its overcurrent device at 30 A. In aluminum, 10 AWG is listed at 30 A (75 °C) and 35 A (90 °C) in the Cerrowire chart (2017 NEC). Check derating if more than three current-carrying conductors share a raceway or the ambient is above 30 °C.
Can I use the 90 °C column for THHN wire?
Usually only as the starting point for derating. Equipment terminals for 14 AWG to 1 AWG are assumed to be rated 60 °C (1/0 and larger: 75 °C) unless the equipment is marked otherwise (NEC 110.14(C)(1)), and NM-B and UF-B cable is limited to the 60 °C column. The final ampacity is the lowest of the derated value, the terminal limit and the cable-type limit.
What does derating mean for wire?
Table 310.16 assumes at most three current-carrying conductors and an ambient of 30 °C (86 °F). With more conductors the ampacity must be multiplied by an adjustment factor (80 % for 4 to 6 conductors, falling to 35 % for 41 or more), and above 30 °C by a temperature correction factor. For example, 12 AWG THHN with 6 current-carrying conductors: 30 A × 0.80 = 24 A, still protected at no more than 20 A.
Is aluminum wire ampacity lower than copper?
Yes. For the same size, aluminum is rated lower: 6 AWG is 65 A in copper and 50 A in aluminum at 75 °C; 4/0 is 230 A copper and 180 A aluminum. So aluminum has to be larger for the same current: 4/0 aluminum (180 A at 75 °C) carries about what 2/0 copper (175 A) does.