UL 248 fuse classes (CC, J, RK1, RK5, T, L, G, H, K) with voltage, amp range and interrupting rating; blade fuse colors; IEC gG/aM and miniature F/T fuse letters.
Updated Oct 6, 20267 min read
In North America, branch-circuit fuses are grouped into UL 248 classes: Class CC (600 V, 1/10–30 A), Class J (600 V, 1–600 A), Class RK1 and RK5 (250 or 600 V, up to 600 A), Class T (300 V up to 1,200 A, 600 V up to 800 A) and Class L (600 V, 601–6,000 A) all interrupt at least 200 kA, Class G 100 kA, while old-style Class H fuses interrupt only 10 kA. Car blade fuses are 32 V DC parts color-coded by amps (10 A red, 15 A blue, 20 A yellow, 30 A green). IEC fuses are labelled with letters instead: gG/aM for low-voltage power fuses and F/T for miniature glass fuses. Figures are from Eaton Bussmann and Littelfuse technical documents and the IEC standards they cite; the fuse maker's data sheet, the equipment instructions and your local electrical code govern. To work out a fuse size from a load, use the Fuse Calculator.
UL 248 fuse classes (600 V or less)
UL class
Voltage (V AC)
Current range (A)
Interrupting rating, minimum (kA)
Holder rejection
CC
600
1/10–30
200
Yes
CF
600
1–100
200 (Class J performance)
Yes (by amp case size)
G
600 (½–20 A); 480 (25–60 A)
½–60
100
Yes (length varies with rating)
H
250 or 600
Up to 600
10
No
J
600
1–600
200
Yes
K (K1, K5, K9)
250 or 600
Up to 600
50, 100 or 200
No (Class H size)
L
600
601–6,000
200
Bolted, not in clips
RK1, RK5
250 or 600
1/10–600
200
Yes (Class R clips)
T
300 (to 1,200 A); 600 (to 800 A)
1–1,200
200
Yes (very small body)
Plug fuses (Edison base, Type S)
125
Up to 30
10
Type S only
Reading the UL class table
Current-limiting. Classes CC, CF, G, J, L, RK1, RK5 and T are current-limiting: in their current-limiting range they clear a short circuit in less than half a cycle and hold the peak let-through current well below what the circuit could deliver. Class K fuses limit current but are not marked "current-limiting" because they have no rejection feature; Class H fuses are not current-limiting.
Rejection. Class R fuses have a notched blade or a ferrule groove so that Class R clips reject Class H and K fuses (lower interrupting rating); Class R fuses still fit ordinary H/K clips, so they can upgrade old equipment. Class J, CC, G, T and CF use unique dimensions instead. This stops a 10 kA fuse from being fitted where a 200 kA fuse is needed.
Sizes. Class CC is 13/32 in × 1-1/2 in (about 10 × 38 mm). Class G is 13/32 in in diameter, 1-5/16 in long at 15 A and below, rising to 2-1/4 in at 35–60 A, so a larger rating cannot be fitted in a smaller holder. Class CF (Bussmann CUBEFuse) is finger-safe and comes in 30, 60 and 100 A case sizes.
RK1 vs RK5. Both share Class H dimensions and a 200 kA minimum rating; RK1 fuses let through less energy on a short circuit (Bussmann calls RK5 a "moderate degree of current limitation").
Product ratings can exceed the class minimum. For example, Bussmann Low-Peak Class J and RK1 fuses are rated 300 kA, against the 200 kA class minimum.
Plug fuses. Types T (time-delay) and W (fast-acting) have Edison (light-bulb) bases; Type S has a base thread that changes with the amp rating, so a larger fuse will not screw into a smaller adapter. Bussmann does not recommend Type W for circuits with motor loads.
Time-delay, fast-acting and dual-element fuses
Time-delay
A built-in delay passes temporary, harmless inrush current without opening, but the fuse still opens on sustained overloads and short circuits. Use for motors, transformers and solenoids.
Fast-acting
Opens on overload and short circuit very quickly; not designed to withstand the temporary overloads of some loads when sized close to full-load current.
Dual-element
Two elements in series: a spring-actuated overload element that operates on overloads up to 5–6 times the rating, and a short-circuit section for faults up to the interrupting rating.
Example delay
Bussmann KRP-C Class L time-delay fuse: at least 4 s at 5 times its rating. Class T fuses are fast-acting.
High-speed
Semiconductor fuses have no intentional delay in the overload range and open as fast as possible on short circuits, to protect diodes, thyristors and drives (IEC marks these "aR").
IEC low-voltage fuse codes (gG, gM, aM)
First letter g
Full-range breaking capacity: the fuse-link can break every current that melts its element, up to its rated breaking capacity.
First letter a
Partial-range breaking capacity: breaks currents from the lowest value on its time-current curve up to its breaking capacity. Used for short-circuit protection, with another switching device for small overcurrents.
gG
Full range, general application (cables, general circuits).
gM
Full range, for motor circuits. Carries two current values, e.g. "In M Ich": the continuous rating and the G-characteristic current.
aM
Partial range, for motor circuits (short-circuit back-up).
Others
Later parts of IEC 60269 add categories such as gPV for photovoltaic strings (IEC 60269-6) and aR for semiconductor protection.
Miniature fuses: IEC 60127 letters
Symbol
Meaning
Color band (if color-coded)
FF
Very quick-acting
Black
F
Quick-acting
Red
M
Medium time-lag
Yellow
T
Time-lag
Blue
TT
Long time-lag
Grey
H
High breaking capacity (1,500 A for 5 × 20 mm, 250 V)
—
L
Low breaking capacity (35 A or 10 × In, whichever is greater)
—
E
Enhanced breaking capacity (for prospective fault currents above 35 A up to 150 A)
—
5 × 20 mm fuses: F vs T pre-arcing time limits
Current (× rated In)
F, quick-acting, 50 mA–4 A (s or ms)
T, time-lag, 100–800 mA (s or ms)
2.1 × In
Maximum 30 min
Maximum 30 min
2.75 × In
10 ms to 2 s
250 ms to 80 s
4 × In
3 ms to 300 ms
50 ms to 5 s
10 × In
Maximum 20 ms
5 ms to 150 ms
How the miniature-fuse figures are marked
The letter for speed goes before the current rating, and the breaking-capacity letter between current and voltage: T 3.15 A H 250 V is a 3.15 A time-lag, high-breaking-capacity, 250 V fuse.
The F column is IEC 60127-2 standard sheet 1 (5 × 20 mm, quick-acting, high breaking capacity); the T column is standard sheet 5 (5 × 20 mm, time-lag, high breaking capacity). Above 800 mA, sheet 5 allows 750 ms to 80 s at 2.75 × In. Other sheets (low breaking capacity, 6.3 × 32 mm) have their own limits.
Pre-arcing (melting) time is the time until the element melts; the arc then takes a little longer to clear, and melting plus arcing time is the clearing time (Bussmann glossary).
Automotive blade fuses: color code
Rating (A)
Housing color
ATO / ATOF (1–40 A)
MINI (2–30 A)
1
Black
Yes
—
2
Grey
Yes
Yes
3
Violet
Yes
Yes
4
Pink
Yes
Yes
5
Tan
Yes
Yes
7.5
Brown
Yes
Yes
10
Red
Yes
Yes
15
Blue
Yes
Yes
20
Yellow
Yes
Yes
25
Natural (clear)
Yes
Yes
30
Green
Yes
Yes
35
Dark green
Yes
—
40
Orange
Yes
—
Blade fuse ratings and opening times
Voltage
32 V DC (ATOF, ATO Ag, MINI and MAXI).
Interrupting rating
1,000 A at 32 V DC.
Standards
ATOF: SAE J1284 and ISO 8820-3. MINI: SAE J2077 and ISO 8820-3. MAXI: SAE J1888, ISO 8820-3 and DIN 72581-3.
Size
ATOF body 19.1 mm wide (Littelfuse outline, reference only).
110 % of rating
Must carry it for at least 360,000 s (100 h).
135 %
Opens in 0.75 s to 600 s (ATOF 1 and 2 A: 0.35 s to 600 s).
200 %
Opens in 0.15 s to 5 s (ATOF 1 and 2 A: 0.1 s to 5 s).
350 %
MINI: 0.08 s to 0.5 s.
600 %
MINI: 0.03 s to 0.1 s. ATOF: 0.1 s maximum (1–30 A), 0.15 s maximum (35 and 40 A).
Continuous load
Littelfuse recommends a continuous current of at most 80 % of the rating, less at high ambient temperatures (its datasheets give derating tables).
Selection checklist
Voltage rating must be at least the circuit's open-circuit voltage. Exceeding it impairs the fuse's ability to clear an overload or short circuit safely. AC and DC ratings are separate; many fuses have a lower DC rating (for example, Bussmann LPJ Class J: 600 V AC, 300 V DC).
Interrupting rating (breaking capacity) must be at least the fault current available where the fuse is installed: the NEC defines it as the highest current at rated voltage the device is intended to interrupt under standard test conditions.
Current rating: keep the normal continuous load within the maker's recommended limit (80 % for Littelfuse automotive fuses), and never above what the wire can carry. Under NEC 240.4(D), 14, 12 and 10 AWG copper may be protected at no more than 15, 20 and 30 A. See AWG Current Capacity.
Speed: time-delay for motor, transformer and solenoid inrush; fast-acting or high-speed for semiconductors and other sensitive loads.
Replace like with like: same class, voltage, current and speed. A higher-rated fuse removes the protection the wire depends on.
Sources
All documents were downloaded and read on 6 October 2026. Earlier versions of this page gave unsourced fuse-size and speed-class figures (for example "FF blows in under 100 ms at 10 ×" and "125–150 % of steady load"); they have been replaced by the figures below.
Eaton, Bussmann series Selecting Protective Devices (SPD), 2018 edition (document bus-ele-br-3002-spd-2017): branch-circuit fuse selection chart (Table 3.1.6.1.d), Class CC/CF/G/J/L/RK1/RK5/T product pages and the glossary of fuse classes (section 9.2). eaton.com/content/dam/eaton/markets/machinebuilding/protect-personnel-assets-and-machine-reliability/documents/documents-english-language/bus-ele-br-3002-spd-2017_safe.pdf
Littelfuse, ATOF Blade Fuses Rated 32V datasheet, REV07272021, and MINI Blade Fuses Rated 32V datasheet, REV11042021 (ratings, housing-color swatches, time-current tables). Colors are named from the datasheet swatches. littelfuse.com/-/media/automotive/datasheets/fuses/passenger-car-and-commercial-vehicle/blade-fuses/
Littelfuse, MAXI Blade Fuse Rated 32V datasheet (standards and ratings), and Automotive Fuseology (recommended continuous current, derating), littelfuse.com, read from Internet Archive copies.
Bureau of Indian Standards, IS 13703 (Part 1): 1993, Low-voltage fuses … Part 1: General requirements, identical with IEC 269-1 (1986), clause 2.2 and 5.7.1 (g/a fuse-links, gG, gM, aM). Public copy: archive.org/details/gov.in.is.13703.1.1993
Bureau of Indian Standards, IS/IEC 60127-1: 2006, Miniature fuses, Part 1 (symbols FF, F, M, T, TT and color code) and IS/IEC 60127-2: 2003, Part 2: Cartridge fuse-links, identical with IEC 60127-2:2003 (standard sheets 1 and 5, breaking-capacity letters H, L, E). Public copies: archive.org/details/gov.in.is.iec.60127.1.2006, archive.org/details/gov.in.is.iec.60127.2.2003
Frequently asked questions
What is the difference between a fast-acting and a time-delay fuse?
A time-delay fuse has a built-in delay that lets harmless inrush currents (motors, transformers) pass but still opens on sustained overloads and short circuits; a fast-acting fuse opens on overloads and short circuits very quickly and is not designed to ride through inrush. For 5 × 20 mm fuses under IEC 60127-2, a quick-acting (F) 1 A fuse must melt within 20 ms at 10 times its rating, while a time-lag (T) 1 A fuse must take at least 10 ms and at most 150 ms.
What do the colors of car blade fuses mean?
The color shows the current rating. On Littelfuse ATO/ATOF and MINI blade fuses: 2 A grey, 3 A violet, 4 A pink, 5 A tan, 7.5 A brown, 10 A red, 15 A blue, 20 A yellow, 25 A natural (clear), 30 A green; ATO adds 1 A black, 35 A dark green and 40 A orange. All are rated 32 V DC with a 1,000 A interrupting rating.
What is a Class J fuse?
A UL Class J fuse is a 600 V AC, current-limiting branch-circuit fuse made from 1 to 600 A with an interrupting rating of at least 200 kA. Its dimensions are unique, so Class J holders reject every other fuse class, which keeps the voltage and interrupting ratings from being downgraded during replacement.
What do gG and aM mean on a fuse?
They are IEC 60269 fuse-link codes. The first letter is the breaking range: g = full range (clears every current that melts the element), a = partial range (short-circuit protection only, used with another device for overloads). The second letter is the utilization category: G = general application, M = motor circuits. So gG is a general-purpose full-range fuse and aM a motor back-up fuse.
How do I choose a fuse rating?
Voltage rating at least the circuit voltage; interrupting rating at least the fault current available at that point; current rating high enough that the normal load stays within the maker's continuous limit (Littelfuse recommends at most 80 % of rating for its automotive fuses), but low enough to protect the smallest wire (for example 20 A maximum on 12 AWG copper under NEC 240.4(D)). Local code and the equipment maker's instructions govern.
Was this article helpful?
Cookies & ads
Tools run client-side — your inputs stay in your browser. No ad network is installed, so no ad cookies are set. Choose what this site may store on your device. Privacy · Cookies
Essential StorageTheme, consent state, CSRF tokens. Required for the site to work.
Always on
PersonalizationRecently used tools, custom colors, accessibility preferences. Stored locally on your device.
AdvertisingOnly applies if an ad network is installed. None is today, so no ad cookies are set either way. Details.
AnalyticsAggregate, anonymous page-view counts so we know which tools to improve.
AI IntegrationStores your API key locally for optional AI features. Key never leaves your device.