Harmonic distortion in power systems and audio — THD, triplens, and standard limits.
Updated Apr 19, 20262 min read
Definitions
Fundamental
The signal's main frequency (e.g., 60 Hz)
Harmonic (n-th)
Integer multiple: 120, 180, 240, … Hz
Sub-harmonic
Below fundamental (e.g., 30 Hz) — rare
Interharmonic
Non-integer multiple
THD
√(Σ V_h² for h ≥ 2) / V_1 — as ratio or %
Triplens
3rd, 9th, 15th … — especially bad in 3-phase (add in neutral)
Typical THD in audio
System
THD
Studio mic preamp
< 0.001%
Good home amplifier
< 0.01%
Consumer amp
< 0.1%
Guitar tube amp (clean)
1–5%
Guitar tube amp (overdrive)
10–50%
Dynamic microphone
< 1% (normal SPL)
Power quality limits
Standard
Application
THD limit
IEEE 519 (< 1 kV)
Utility bus — individual harmonic
5%
IEEE 519 (< 1 kV)
Utility bus — total
8%
EN 50160
Supply voltage (95% week)
8%
IEC 61000-3-2 Class A
Professional equipment
Per-harmonic mA limits
IEC 61000-3-2 Class D
PC, TV (< 600 W)
Per-harmonic proportional to P
Mitigation
Passive filters: LC-tuned traps at specific harmonics.
Active filters: inject anti-harmonic currents.
Line reactors: series inductance reduces harmonics from rectifier loads.
12-pulse or multi-pulse rectifiers: cancel low-order harmonics.
Active PFC: forces input current to follow voltage — reduces harmonics at the source.
Worked example: a rectifier load
A single-phase rectifier load on a 60 Hz supply draws a fundamental current of 10 A with a 3rd harmonic (180 Hz) of 3 A, a 5th (300 Hz) of 2 A and a 7th (420 Hz) of 1 A. Current THD = √(3² + 2² + 1²) / 10 = √14 / 10 = 3.74 / 10 = 37.4%. The total RMS current is √(10² + 14) = √114 = 10.68 A, 6.8% higher than the fundamental alone, so the wiring and breaker see more current than a clamp meter tuned to 60 Hz would suggest. The distortion factor is 1 / √(1 + 0.374²) = 1 / √1.14 = 0.936, so even if the fundamental current is perfectly in phase with the voltage, the power factor cannot exceed 0.94.
Neutral current: in a three-phase four-wire system the 60 Hz fundamentals cancel in the neutral, but the triplen harmonics do not, because they are in phase in all three conductors. With 3 A of 3rd harmonic in each phase, the neutral carries 3 × 3 = 9 A of 180 Hz current. Heavily loaded rectifier circuits can load the neutral beyond the phase conductors, so the neutral must not be undersized.
Practical points
Voltage THD and current THD are different. Voltage limits (EN 50160, the IEEE 519 voltage table) apply at the supply point. Current THD of 30 to 100% on a single load is normal; what matters is the current distortion relative to the maximum demand load current at the point of common coupling.
Measure with a true-RMS analyzer that reports individual harmonics up to at least the 25th (1.5 kHz at 60 Hz) and a THD figure that says which denominator it uses.
Look at the heat first. Overheated neutrals, warm transformers and tripped capacitor-bank fuses are typical signs that harmonics are higher than expected. Capacitor banks can resonate with the system inductance at a harmonic order, amplifying it.
Was this article helpful?
Cookies & ads
Tools run client-side — your inputs stay in your browser. No ad network is installed, so no ad cookies are set. Choose what this site may store on your device. Privacy · Cookies
Essential StorageTheme, consent state, CSRF tokens. Required for the site to work.
Always on
PersonalizationRecently used tools, custom colors, accessibility preferences. Stored locally on your device.
AdvertisingOnly applies if an ad network is installed. None is today, so no ad cookies are set either way. Details.
AnalyticsAggregate, anonymous page-view counts so we know which tools to improve.
AI IntegrationStores your API key locally for optional AI features. Key never leaves your device.