Electronics

Harmonics & THD Reference

Harmonic distortion in power systems and audio — THD, triplens, and standard limits.

Definitions

FundamentalThe signal's main frequency (e.g., 60 Hz)
Harmonic (n-th)Integer multiple: 120, 180, 240, … Hz
Sub-harmonicBelow fundamental (e.g., 30 Hz) — rare
InterharmonicNon-integer multiple
THD√(Σ V_h² for h ≥ 2) / V_1 — as ratio or %
Triplens3rd, 9th, 15th … — especially bad in 3-phase (add in neutral)

Typical THD in audio

SystemTHD
Studio mic preamp< 0.001%
Good home amplifier< 0.01%
Consumer amp< 0.1%
Guitar tube amp (clean)1–5%
Guitar tube amp (overdrive)10–50%
Dynamic microphone< 1% (normal SPL)

Power quality limits

StandardApplicationTHD limit
IEEE 519 (< 1 kV)Utility bus — individual harmonic5%
IEEE 519 (< 1 kV)Utility bus — total8%
EN 50160Supply voltage (95% week)8%
IEC 61000-3-2 Class AProfessional equipmentPer-harmonic mA limits
IEC 61000-3-2 Class DPC, TV (< 600 W)Per-harmonic proportional to P

Mitigation

  • Passive filters: LC-tuned traps at specific harmonics.
  • Active filters: inject anti-harmonic currents.
  • Line reactors: series inductance reduces harmonics from rectifier loads.
  • 12-pulse or multi-pulse rectifiers: cancel low-order harmonics.
  • Active PFC: forces input current to follow voltage — reduces harmonics at the source.

Worked example: a rectifier load

A single-phase rectifier load on a 60 Hz supply draws a fundamental current of 10 A with a 3rd harmonic (180 Hz) of 3 A, a 5th (300 Hz) of 2 A and a 7th (420 Hz) of 1 A. Current THD = √(3² + 2² + 1²) / 10 = √14 / 10 = 3.74 / 10 = 37.4%. The total RMS current is √(10² + 14) = √114 = 10.68 A, 6.8% higher than the fundamental alone, so the wiring and breaker see more current than a clamp meter tuned to 60 Hz would suggest. The distortion factor is 1 / √(1 + 0.374²) = 1 / √1.14 = 0.936, so even if the fundamental current is perfectly in phase with the voltage, the power factor cannot exceed 0.94.

Neutral current: in a three-phase four-wire system the 60 Hz fundamentals cancel in the neutral, but the triplen harmonics do not, because they are in phase in all three conductors. With 3 A of 3rd harmonic in each phase, the neutral carries 3 × 3 = 9 A of 180 Hz current. Heavily loaded rectifier circuits can load the neutral beyond the phase conductors, so the neutral must not be undersized.

Practical points

  • Voltage THD and current THD are different. Voltage limits (EN 50160, the IEEE 519 voltage table) apply at the supply point. Current THD of 30 to 100% on a single load is normal; what matters is the current distortion relative to the maximum demand load current at the point of common coupling.
  • Measure with a true-RMS analyzer that reports individual harmonics up to at least the 25th (1.5 kHz at 60 Hz) and a THD figure that says which denominator it uses.
  • Look at the heat first. Overheated neutrals, warm transformers and tripped capacitor-bank fuses are typical signs that harmonics are higher than expected. Capacitor banks can resonate with the system inductance at a harmonic order, amplifying it.
Was this article helpful?