Power triangle
| Real (active) P | Watts (W) — does actual work |
|---|---|
| Reactive Q | VAR — stored/returned, no work |
| Apparent S | VA = √(P² + Q²) — what the supply must provide |
| Power factor | PF = P / S = cos φ (for sinusoidal) |
| Leading vs lagging | Capacitive load leads; inductive load lags |
Typical PF values
| Load | PF |
|---|---|
| Incandescent lamp | 1.00 |
| Resistive heater | 1.00 |
| Induction motor (full load) | 0.80–0.90 |
| Induction motor (no load) | 0.10–0.30 |
| Uncorrected fluorescent | 0.40–0.60 |
| Switching PSU (cheap) | 0.50–0.70 |
| Switching PSU (with PFC) | 0.90–0.99 |
| LED driver (good) | 0.90–0.99 |
Why it matters
- Poor PF forces utility to deliver extra current — commercial customers are billed for it (kVA or PF penalties).
- Cable / transformer sizing uses apparent power S, not real power P.
- Power factor correction (PFC): add capacitors for inductive loads, inductors for capacitive — or active PFC for electronic loads.
- Non-sinusoidal loads (rectifiers, PC power supplies) have harmonics — PF involves total harmonic distortion: PF = cos φ · (1 / √(1 + THD²)).
Worked example: correcting a motor load
A single-phase 240 V, 60 Hz shop draws P = 5 kW at a power factor of 0.80 lagging. Apparent power S = 5 / 0.80 = 6.25 kVA, so the current is 6,250 / 240 = 26.0 A. At unity power factor the same 5 kW would need only 5,000 / 240 = 20.8 A. Reactive power Q = √(6.25² − 5²) = √14.06 = 3.75 kvar.
To correct to 0.95, S becomes 5 / 0.95 = 5.263 kVA and Q becomes √(5.263² − 5²) = √2.70 = 1.64 kvar. The capacitor bank must supply the difference, 3.75 − 1.64 = 2.11 kvar. The same figure comes from P × (tan φ1 − tan φ2) = 5 × (0.75 − 0.329) = 2.11 kvar. The capacitance is C = Q / (2π f V²) = 2,110 / (377 × 240²) = 2,110 / 21,715,200 = 97 µF. The new current is 5,263 / 240 = 21.9 A, a reduction of about 16%.
Common mistakes
- Over-correcting. A fixed capacitor bank sized for full load will push a lightly loaded motor into a leading power factor, which can raise the voltage and cause resonance. Use automatic stepped banks for varying loads.
- Using capacitors on harmonic-rich loads. Capacitors lower the resonant frequency of the network and can amplify harmonics. Use detuned (reactor-protected) banks where drives or rectifiers are present.
- Mixing displacement and true power factor. The cos φ figure on a motor nameplate (displacement) ignores harmonics. True power factor is P / S measured with a power analyzer and includes distortion.
- Forgetting three-phase arithmetic. For three-phase loads use I = S / (√3 × Vline), not S / V.