Electronics

Power Factor Reference

Real, reactive, and apparent power — the power triangle and typical load PF values.

Power triangle

Real (active) PWatts (W) — does actual work
Reactive QVAR — stored/returned, no work
Apparent SVA = √(P² + Q²) — what the supply must provide
Power factorPF = P / S = cos φ (for sinusoidal)
Leading vs laggingCapacitive load leads; inductive load lags

Typical PF values

LoadPF
Incandescent lamp1.00
Resistive heater1.00
Induction motor (full load)0.80–0.90
Induction motor (no load)0.10–0.30
Uncorrected fluorescent0.40–0.60
Switching PSU (cheap)0.50–0.70
Switching PSU (with PFC)0.90–0.99
LED driver (good)0.90–0.99

Why it matters

  • Poor PF forces utility to deliver extra current — commercial customers are billed for it (kVA or PF penalties).
  • Cable / transformer sizing uses apparent power S, not real power P.
  • Power factor correction (PFC): add capacitors for inductive loads, inductors for capacitive — or active PFC for electronic loads.
  • Non-sinusoidal loads (rectifiers, PC power supplies) have harmonics — PF involves total harmonic distortion: PF = cos φ · (1 / √(1 + THD²)).

Worked example: correcting a motor load

A single-phase 240 V, 60 Hz shop draws P = 5 kW at a power factor of 0.80 lagging. Apparent power S = 5 / 0.80 = 6.25 kVA, so the current is 6,250 / 240 = 26.0 A. At unity power factor the same 5 kW would need only 5,000 / 240 = 20.8 A. Reactive power Q = √(6.25² − 5²) = √14.06 = 3.75 kvar.

To correct to 0.95, S becomes 5 / 0.95 = 5.263 kVA and Q becomes √(5.263² − 5²) = √2.70 = 1.64 kvar. The capacitor bank must supply the difference, 3.75 − 1.64 = 2.11 kvar. The same figure comes from P × (tan φ1 − tan φ2) = 5 × (0.75 − 0.329) = 2.11 kvar. The capacitance is C = Q / (2π f V²) = 2,110 / (377 × 240²) = 2,110 / 21,715,200 = 97 µF. The new current is 5,263 / 240 = 21.9 A, a reduction of about 16%.

Common mistakes

  • Over-correcting. A fixed capacitor bank sized for full load will push a lightly loaded motor into a leading power factor, which can raise the voltage and cause resonance. Use automatic stepped banks for varying loads.
  • Using capacitors on harmonic-rich loads. Capacitors lower the resonant frequency of the network and can amplify harmonics. Use detuned (reactor-protected) banks where drives or rectifiers are present.
  • Mixing displacement and true power factor. The cos φ figure on a motor nameplate (displacement) ignores harmonics. True power factor is P / S measured with a power analyzer and includes distortion.
  • Forgetting three-phase arithmetic. For three-phase loads use I = S / (√3 × Vline), not S / V.
Was this article helpful?