What happens in a short circuit — I²t, interrupting ratings, and protection.
Updated Apr 19, 20262 min read
Fault current
I_fault
= V_source / R_loop
Loop impedance
Source impedance + wiring + contact — usually milliohms to ohms
Prospective
Worst-case current assuming zero-impedance fault
Let-through
Current actually passed before a fuse opens (reduced by I²t limiting)
Energy and heat
I²t
Thermal stress on wires and devices — integral of I² over duration
Wire damage
Occurs quickly — adiabatic limit I²t ≤ k²S² (k = 115 for PVC-insulated copper, S in mm²)
Arc flash
Fault at higher voltage generates plasma; separate hazard — requires IE analysis
Protective devices
Device
Typical clearing time
Notes
Fast-blow fuse
< 10 ms
Let-through I²t limited
Slow-blow fuse
100 ms to seconds
Tolerates inrush
Circuit breaker
< 40 ms (instantaneous trip)
Resettable
eFuse (IC)
< 10 µs
Electronic, very fast; low current
PTC (resettable)
seconds
Self-resets when cool
Crowbar SCR
< 1 ms
OVP — shorts rail to trip upstream fuse
Foldback current limit
continuous
Limits into short, may not clear
Selection checklist
Rating > prospective fault current: interrupt rating must exceed the maximum fault at the device location.
Coordination: downstream devices should clear first so upstream stays energized.
Wire size: selected so short-circuit current doesn't exceed the wire's I²t withstand.
Battery systems: huge prospective current (kA range) — use DC-rated fuses with proper interrupt rating.
Worked examples
Prospective fault current: a 12 V lead-acid battery with 10 milliohms of internal resistance, connected through 5 milliohms of cable and connections, has a loop resistance of 15 milliohms. A dead short draws I = 12 / 0.015 = 800 A. A small automotive fuse is not rated to interrupt that on a high-energy battery bank, so a battery system needs a fuse with a DC interrupt rating well above the expected fault, typically thousands of amps for a large bank. On a mains circuit with a loop impedance of 0.5 ohm, the 230 V fault current is 230 / 0.5 = 460 A.
Will the wire survive? For short faults (under about 5 seconds) the heating is nearly adiabatic and the standard check is I²t ≤ k²S², with k = 115 for PVC-insulated copper (IEC 60364-4-43) and S in mm². A 2.5 mm² conductor can take k²S² = 13,225 × 6.25 = 82,656 A²s. At a 1,000 A fault the protection must clear within 82,656 / 1,000² = 0.083 s. A breaker that opens in 10 ms lets through only about 10,000 A²s at 1,000 A, which is safe, while a slow-blow fuse that takes a second to blow at that current does not protect the wire.
Practical points
Fault current falls with distance. Cable resistance adds to the loop, so the fault current at the far end of a long run is much lower than at the panel. Check that the protection still trips at the remote end, not only that the cable survives at the near end.
Low-power supplies need a current limit, not just a fuse. A power supply that folds back or limits at 2 A will not blow a 10 A fuse; the wire is safe but the short sits there heating the source.
Size the breaker for the wire, not the load. A 20 A breaker on 1.5 mm² wire does not protect the wire against overload.
Test safely. Never short a battery bank to see what happens. Verify with calculation and a rated test setup, wearing insulated tools and eye protection.
Was this article helpful?
Cookies & ads
Tools run client-side — your inputs stay in your browser. No ad network is installed, so no ad cookies are set. Choose what this site may store on your device. Privacy · Cookies
Essential StorageTheme, consent state, CSRF tokens. Required for the site to work.
Always on
PersonalizationRecently used tools, custom colors, accessibility preferences. Stored locally on your device.
AdvertisingOnly applies if an ad network is installed. None is today, so no ad cookies are set either way. Details.
AnalyticsAggregate, anonymous page-view counts so we know which tools to improve.
AI IntegrationStores your API key locally for optional AI features. Key never leaves your device.