Electronics

Short Circuit Basics

What happens in a short circuit — I²t, interrupting ratings, and protection.

Fault current

I_fault= V_source / R_loop
Loop impedanceSource impedance + wiring + contact — usually milliohms to ohms
ProspectiveWorst-case current assuming zero-impedance fault
Let-throughCurrent actually passed before a fuse opens (reduced by I²t limiting)

Energy and heat

I²tThermal stress on wires and devices — integral of I² over duration
Wire damageOccurs quickly — adiabatic limit I²t ≤ k²S² (k = 115 for PVC-insulated copper, S in mm²)
Arc flashFault at higher voltage generates plasma; separate hazard — requires IE analysis

Protective devices

DeviceTypical clearing timeNotes
Fast-blow fuse< 10 msLet-through I²t limited
Slow-blow fuse100 ms to secondsTolerates inrush
Circuit breaker< 40 ms (instantaneous trip)Resettable
eFuse (IC)< 10 µsElectronic, very fast; low current
PTC (resettable)secondsSelf-resets when cool
Crowbar SCR< 1 msOVP — shorts rail to trip upstream fuse
Foldback current limitcontinuousLimits into short, may not clear

Selection checklist

  • Rating > prospective fault current: interrupt rating must exceed the maximum fault at the device location.
  • Coordination: downstream devices should clear first so upstream stays energized.
  • Wire size: selected so short-circuit current doesn't exceed the wire's I²t withstand.
  • Battery systems: huge prospective current (kA range) — use DC-rated fuses with proper interrupt rating.

Worked examples

Prospective fault current: a 12 V lead-acid battery with 10 milliohms of internal resistance, connected through 5 milliohms of cable and connections, has a loop resistance of 15 milliohms. A dead short draws I = 12 / 0.015 = 800 A. A small automotive fuse is not rated to interrupt that on a high-energy battery bank, so a battery system needs a fuse with a DC interrupt rating well above the expected fault, typically thousands of amps for a large bank. On a mains circuit with a loop impedance of 0.5 ohm, the 230 V fault current is 230 / 0.5 = 460 A.

Will the wire survive? For short faults (under about 5 seconds) the heating is nearly adiabatic and the standard check is I²t ≤ k²S², with k = 115 for PVC-insulated copper (IEC 60364-4-43) and S in mm². A 2.5 mm² conductor can take k²S² = 13,225 × 6.25 = 82,656 A²s. At a 1,000 A fault the protection must clear within 82,656 / 1,000² = 0.083 s. A breaker that opens in 10 ms lets through only about 10,000 A²s at 1,000 A, which is safe, while a slow-blow fuse that takes a second to blow at that current does not protect the wire.

Practical points

  • Fault current falls with distance. Cable resistance adds to the loop, so the fault current at the far end of a long run is much lower than at the panel. Check that the protection still trips at the remote end, not only that the cable survives at the near end.
  • Low-power supplies need a current limit, not just a fuse. A power supply that folds back or limits at 2 A will not blow a 10 A fuse; the wire is safe but the short sits there heating the source.
  • Size the breaker for the wire, not the load. A 20 A breaker on 1.5 mm² wire does not protect the wire against overload.
  • Test safely. Never short a battery bank to see what happens. Verify with calculation and a rated test setup, wearing insulated tools and eye protection.
Was this article helpful?