Key numbers
| STC | 1 000 W/m², AM1.5, cell 25 °C — panel rated power is at STC |
|---|---|
| NOCT | 800 W/m², 20 °C ambient, 1 m/s wind — more realistic rating |
| Peak sun hours | Daily kWh/m² equivalent of 1 kW/m² — 4–6 for most of US |
| Panel area | Typical 400 W residential panel ≈ 2 m² (200 W/m²) |
| System loss | Allow 20–25% (wiring, inverter, temp, soiling) |
System sizing
| Daily energy | E (Wh) = P_array (W) × peak_sun_hours × (1 − losses) |
|---|---|
| Array size | P_array = daily_load_Wh / (PSH × efficiency) |
| Battery (daily cycle) | Capacity Ah = daily_Wh / (V_bank × DoD × η) |
| Days of autonomy | Multiply battery by N days for cloudy weather |
| Charge controller amps | Array short-circuit current × 1.25 safety margin |
Battery depth of discharge
| Chemistry | Max DoD | Cycle life (typical) |
|---|---|---|
| Lead-acid (flooded) | 50% | ~500 cycles |
| Lead-acid (AGM) | 50% | ~800 cycles |
| LiFePO₄ | 80–90% | 2 000–5 000 cycles |
| Li-ion (NMC) | 80% | ~1 000 cycles |
Worked example: a small off-grid cabin
The daily load is 2,000 Wh and the worst month gives 4.5 peak sun hours. With 25% system losses the efficiency factor is 0.75. Array size = 2,000 / (4.5 × 0.75) = 593 W, so two 300 W panels (600 W) just meet the need, with no margin. A third panel would give about 50% reserve for cloudy days.
Battery: on a 12 V bank with lead-acid limited to 50% depth of discharge and 85% round-trip efficiency, one day of storage needs 2,000 / (12 × 0.50 × 0.85) = 392 Ah, and two days of autonomy needs 784 Ah. With LiFePO₄ at 80% usable and 95% efficiency the same day needs 2,000 / (12 × 0.80 × 0.95) = 219 Ah (real LiFePO₄ banks are 12.8 V nominal, which cuts the figure slightly). The lithium bank is roughly half the size and, being cycled more deeply, lasts several times as many cycles.
Charge controller: if each panel has a short-circuit current of 9 A and the two are in parallel, the array provides 18 A. With the 1.25 safety margin from the table above, the controller input must handle 22.5 A, so choose a 30 A unit. Many electrical codes (for example the US NEC) apply a second 125% factor for continuous current, so check local rules.
Practical points
- Size for the worst month, not the average. A system that works in July and fails in December is undersized.
- Hot panels make less. A cell at 65 °C is 40 °C over the 25 °C rating, so with a typical −0.35% per °C the output falls by about 14%. Leave an air gap behind the panel.
- Keep the voltage drop low. At 12 V a 3% drop is only 0.36 V, so low-voltage runs need thick cable. Higher-voltage series strings with an MPPT controller cut the current and the cable cost.
- Check the controller input voltage. Cold weather raises panel open-circuit voltage by roughly 10 to 15% below the 25 °C value, and exceeding the controller maximum destroys it.
- Account for the standby load. The inverter itself draws power all day; an inverter with a 20 W idle draw uses 480 Wh per day, a quarter of this cabin load.
Notes
- Peak sun hours vary by month — size for worst month (typically December in N. Hemisphere).
- Panel temperature rises reduce output ~0.3–0.5% per °C above 25 °C.
- Use MPPT charge controllers above ~100 W arrays — 20–30% more harvest than PWM.