Electronics

Three-Phase Basics

Three-phase power systems — wye vs delta, line vs phase quantities, and common voltages.

Wye (star) vs delta

Wye (Y)Delta (Δ)
NeutralPresentNo neutral
V_line= √3 · V_phase= V_phase
I_line= I_phase= √3 · I_phase
Typical useUtility distribution, 4-wireMotor windings, industrial
Ground faultNeutral gives a return pathUngrounded — harder to detect

Common system voltages

SystemV_lineV_phase
US 120/208 V (wye)208 V120 V
US 277/480 V (wye)480 V277 V
US 240 V delta240 V240 V
EU 230/400 V (wye)400 V230 V
Japan 100/200 V200 V100 V

Power formulas

Real power P= √3 · V_line · I_line · cos φ
Apparent power S= √3 · V_line · I_line
Reactive power Q= √3 · V_line · I_line · sin φ
Phase sequenceABC (positive) or ACB (negative) — motors rotate opposite direction

Worked example: a 480 V motor

A three-phase motor on a 480 V (line-to-line) supply draws 40 A in each line at a power factor of 0.85. Apparent power is S = √3 × 480 × 40 = 1.732 × 19,200 = 33,255 VA, or about 33.3 kVA. Real power is P = S × 0.85 = 28,267 W, about 28.3 kW. Reactive power is Q = S × sin φ, where sin φ = √(1 − 0.85²) = 0.527, so Q ≈ 17.5 kvar. The phase voltage of a wye system is 480 / 1.732 = 277 V, which is why 277 V lighting circuits exist on 480 V services.

If the same motor were wound in delta, each winding would carry 40 / 1.732 = 23.1 A while seeing the full 480 V. The line current is what the breaker and cable must handle, so size those from the line value, not the winding value.

Common mistakes

  • Mixing line and phase values. The √3 in the power formula goes with line-to-line voltage and line current. Using the 277 V phase voltage there under-reports power by 1.732 times.
  • Treating 208 V as 240 V. On a 120/208 V wye system a 240 V single-phase load will run low. Two phases are 120 degrees apart, so line-to-line is 120 × 1.732 = 208 V, not 240 V.
  • Assuming phase order does not matter. Swapping any two lines reverses a three-phase motor. Check rotation with a phase-sequence meter before connecting pumps or compressors.
  • Ignoring imbalance. Uneven single-phase loads push current onto the neutral of a wye system, so a neutral sized for zero current may overheat.

Notes

  • Three-phase delivers constant instantaneous power — ideal for motors (no torque ripple).
  • For the same power, three-phase needs less copper than three single-phase lines combined.
  • Unbalanced loads on a 3-phase system create neutral current (wye) or circulating current (delta).
Was this article helpful?