Mains step-down ratios
| Primary | Secondary | Ratio (p:s) |
|---|---|---|
| 120 V | 12 V | 10 : 1 |
| 120 V | 9 V | 13.3 : 1 |
| 120 V | 5 V | 24 : 1 |
| 240 V | 24 V | 10 : 1 |
| 240 V | 12 V | 20 : 1 |
| 240 V | 5 V | 48 : 1 |
Impedance-matching ratios (audio)
| Primary Z | Secondary Z | Turns ratio |
|---|---|---|
| 8 000 Ω | 8 Ω | ~31.6 : 1 |
| 4 000 Ω | 8 Ω | ~22.4 : 1 |
| 2 500 Ω | 8 Ω | ~17.7 : 1 |
| 600 Ω | 8 Ω | ~8.66 : 1 |
| 600 Ω | 600 Ω | 1 : 1 (isolation) |
Formulas
| Turns ratio n | = N_p / N_s = V_p / V_s |
|---|---|
| Impedance ratio | = n² = Z_p / Z_s |
| Required turns | Determined by core flux density: N = V · 10⁸ / (4.44 · f · B · A) |
Worked examples
Current follows the inverse ratio. A 120 V to 12 V transformer has a turns ratio of 120 / 12 = 10 : 1. If the secondary supplies 2 A at 12 V (24 W), an ideal primary draws 24 / 120 = 0.2 A, which is 2 A divided by 10. Real units draw slightly more because of core and copper losses.
Impedance follows the square. To match an 8 Ω speaker to a 2,500 Ω source, the impedance ratio is 2,500 / 8 = 312.5, so the turns ratio is √312.5 = 17.7 : 1. Seen from the primary, the 8 Ω load looks like 8 × 17.7² = 2,500 Ω. Doubling the turns ratio multiplies the reflected impedance by four, not two.
What a rating really means. A transformer rated 12 V at full load will read higher with nothing connected. With the 5 to 10 percent regulation noted below the table, a 12 V winding can read about 12.6 to 13.2 V unloaded. If you then rectify it, the DC peak is about 12 × 1.414 = 17 V before diode drops, which matters when choosing capacitor voltage ratings.
Common mistakes
- Applying a mains transformer to DC. A steady current produces no changing flux, so there is no output, and the winding resistance alone limits the current and can overheat the primary.
- Quoting the ratio for voltage and forgetting that current and impedance scale differently: current by n, impedance by n squared.
- Running a 60 Hz transformer at a lower frequency. Flux rises as frequency falls, so a 60 Hz design on 50 Hz sees 20 percent more flux and may saturate.
- Choosing by volts alone. The VA rating, not just the voltage, sets how much current the secondary can supply.
Notes
- B is peak flux density (gauss); A is core cross-sectional area (cm²); f is line frequency.
- Real transformers include losses and leakage inductance — no-load voltage is higher than rated full-load voltage by ~5–10%.