Inrush Current Calculator

Work out the switch-on surge of a capacitor, a transformer or a motor. Peak capacitor charging current and the NTC needed to limit it, transformer magnetizing inrush from its kVA, and motor locked-rotor amps from the NEMA code letter.

Calculator Electronics Updated Oct 5, 2026
How to Use
  1. Pick what is being switched on: Capacitor, Transformer or Motor.
  2. Capacitor: choose AC mains (the tool takes the √2 peak) or a DC bus, enter the capacitance, then either the series resistance (to get the peak current) or the largest current you will allow (to get the resistance an NTC must have).
  3. Transformer: enter the kVA, the primary voltage, single- or three-phase, and the inrush multiple from the maker’s data (Square D publishes 3.3× to 26.2× for its dry-type units; 10 is a fair starting point).
  4. Motor: enter the horsepower (or kW), the line voltage and the code letter from the nameplate. Type the nameplate full-load current if you have it, otherwise the tool estimates it from the efficiency and power factor.
  5. Read the readouts and the drawing, press a preset for a worked example, and check Show Work for every step.
Input
× rated current
cycles
kVA/hp locked rotor
%
0 to 1
Presets
Circuit and Inrush
Peak current
—
Time constant
—
Energy to absorb
—
Charge time (5 tau)
—

Worked Example

A power supply on 230 V mains. The bridge rectifier charges 470 µF through 5 Ω of NTC thermistor and wiring. The capacitor charges to the peak of the mains, √2 × 230 = 325.3 V, so the first peak is I = 325.3 ÷ 5 = 65.05 A. The time constant is τ = 5 × 0.00047 = 2.35 ms, the capacitor is 99.3 % charged after 5τ = 11.75 ms, and the NTC absorbs ½ × 0.00047 × 325.3² = 24.86 J.

A 75 kVA transformer. On 480 V three-phase the rated primary current is 75,000 ÷ (√3 × 480) = 90.21 A. Square D lists this size at 10.0× rated current, so the inrush is about 902.1 A (RMS) for roughly 6 cycles, 100 ms at 60 Hz.

A 10 hp motor, code F. Code F means 5.0 to 5.59 kVA per hp with the rotor locked, so 50 to 55.9 kVA. On 480 V three-phase: 50,000 ÷ (√3 × 480) = 60.14 A up to 55,900 ÷ (√3 × 480) = 67.24 A.

The common mistake: using the RMS mains voltage. 230 ÷ 5 gives 46 A, but the capacitor charges to the peak of the sine wave, not to its RMS value, and the worst case is switching on at the peak. The real first peak is 325.3 ÷ 5 = 65.05 A, 41 % higher, and an NTC or fuse sized for 46 A is undersized.

Show Work

Enter values and calculate to see the step-by-step breakdown.

Formulas

Capacitor peak current
Ipk = Vpk ÷ R
Vpk = √2 × VRMS for rectified mains; R is everything in series (NTC, wiring, rectifier, ESR)
Resistance for a limit
R = Vpk ÷ Imax
The cold resistance an NTC needs to hold the peak to Imax
Charging energy
E = ½ × C × Vpk²
Stored in C, and the same again turned to heat in R; the NTC energy rating must cover it
Time constant
τ = R × C
i(t) = Ipk × e−t/τ; 99.3 % charged after 5τ
Transformer inrush
I = k × S ÷ (√3 × V)
k from the maker’s table (RMS multiple of rated primary current); drop the √3 for single-phase
Half-cycle I²t
I²t = I² × 1 ÷ (2f)
The energy a fuse sees in the first half-cycle (8.3 ms at 60 Hz, 10 ms at 50 Hz)
Locked-rotor amps
LRA = code × hp × 1000 ÷ (√3 × V)
code = kVA per hp from the NEMA letter; divide by V alone for single-phase

Where the Numbers Come From

Capacitors. An empty capacitor is close to a short circuit, so a rectifier front end can draw tens or hundreds of amps for a few milliseconds. The usual cure is an NTC thermistor in series. TDK’s EPCOS application note on NTC inrush current limiters explains why it works: the cold disc limits the surge, then self-heats until its resistance falls by a factor of more than 30 to 50, so it wastes little power in normal running. The same note warns that the disc needs 30 seconds to two minutes to cool before it can limit a second switch-on. The sizing rules used here, R = Vpk ÷ Imax and an energy rating of ½ × C × Vpk², are from Vishay Ametherm’s white paper Solutions for Current Protection (document 24002).

Transformers. When a transformer is switched off, its core keeps some flux. Square D’s data bulletin 7400DB0702 (Schneider Electric, 2009) explains that if power returns at a voltage zero crossing, the flux has to swing past saturation and the primary draws a large current limited mainly by winding resistance. The bulletin gives the historical design formula Imax = 2020 × h × Ac × (Bres + 2Bmax − Bsat) ÷ (N × As), which needs core and coil data you rarely have, so it also tabulates measured multiples. Across its 321 dry-type transformers they run from 3.3× to 26.2×. The higher-efficiency designs required by US DOE rules from January 2007 run the core at higher flux density, which pushed inrush up. Impedance matters too: units under 3 % impedance had a median of 16.9×, those at 5 % or more 9.1×. Square D’s EX transformer catalogue (7400CT1501) adds that inrush lasts about 6 cycles, or 0.1 s, and that its breakers are checked to carry the full inrush multiple at 0.01 s.

Motors. A motor at standstill has no back-EMF, so it draws locked-rotor current until it speeds up. NEMA rates this with code letters A to V giving locked-rotor kVA per horsepower. The ranges in this tool are the table printed by Baldor-ABB in How to read a NEMA motor nameplate (9AKK108388), which also says across-the-line starting draws 300 to 600 percent more than full-load running current. Baldor prints code B as 3.15 to 3.55, overlapping the start of code C.

About This Calculator

This calculator covers the three switch-on surges people most often need to size for. For a capacitor it gives the first peak, or the resistance needed to hold the peak to a limit, plus the time constant, charge time and the energy the limiter must absorb, and it draws the decaying current. For a transformer it gives the rated and inrush current, the first half-cycle I²t and how long the inrush lasts. For a motor it turns the nameplate code letter into a locked-rotor current range and compares it with the full-load current.

The transformer multiple and the motor efficiency and power factor are inputs because they vary from unit to unit. The defaults are typical values, not guarantees, so use the maker’s figures for protection settings. The capacitor figures ignore line impedance and the rectifier’s own drop, so real peaks are a little lower. Everything runs in your browser; nothing you enter is sent anywhere.

Related tools: Short Circuit Current Calculator, AC Power Calculator, and Power Factor Calculator.

Frequently Asked Questions

How do I calculate the inrush current of a capacitor?

At switch-on an empty capacitor looks like a short, so the first peak is the peak supply voltage divided by everything in series: I = Vpk ÷ R. On 230 V AC mains the peak is √2 × 230 = 325.3 V, so 5 Ω of NTC and wiring lets 65.05 A through. The current then falls with time constant τ = RC: with 470 µF that is 2.35 ms, and the capacitor is 99.3 % charged after 5τ = 11.75 ms.

How do I size an NTC thermistor for inrush limiting?

Vishay Ametherm’s selection method uses three numbers. The cold resistance is the peak voltage divided by the largest current you will allow, the energy rating is ½ × C × Vpk², and the steady current must stay within the part’s rating. For 120 V AC, 4,700 µF and a 20 A limit that is 169.7 ÷ 20 = 8.49 Ω and ½ × 0.0047 × 169.7² = 67.7 J, so you need a part rated for at least 67.7 J.

How much inrush current does a transformer draw?

It varies far more than most rules of thumb suggest. Square D’s data bulletin 7400DB0702 lists 321 ventilated dry-type transformers from 15 to 1,000 kVA with inrush from 3.3× to 26.2× the rated primary current (RMS), median 11.4×. A 75 kVA, 480 V three-phase unit listed at 10.0× has 90.21 A full-load current, so it draws about 902 A for the first few cycles. Square D says inrush lasts about 6 cycles, or 0.1 s.

What does the code letter on a motor nameplate mean?

It is the locked-rotor apparent power per horsepower, in kVA/hp, defined by NEMA in letters A to V. Code F means 5.0 to 5.59 kVA/hp, so a 10 hp motor draws 50 to 55.9 kVA at standstill. On 480 V three-phase that is 50,000 ÷ (√3 × 480) = 60.14 A up to 67.24 A of locked-rotor current, about 5 to 6 times the running current.

Why does a transformer sometimes trip the breaker and sometimes not?

Because the inrush depends on where on the voltage wave the switch closes and on the flux left in the core. Square D notes that the maximum inrush happens when power is applied at a voltage zero crossing, and that inrush can be zero when the switching point matches the residual flux. Energising a transformer from its secondary (back-feeding) gives two to three times the normal inrush.

How do I use the Inrush Current Calculator?

Just type your numbers. The answer shows up right away — there is no button to press. Change anything and it updates by itself.

Do I need to install or sign up for anything?

Not at all — it runs in the browser with nothing to install and no account. After it loads once, it even works without an internet connection.

Is my information private?

Yes. Everything happens in your browser. Nothing you type is sent to a server or saved anywhere.

Common Use Cases

Power supply fuses

A 230 V supply with 470 µF of bulk capacitance and 5 Ω in series peaks at 65.05 A and dumps 24.86 J into the limiter on every cold start, so the fuse must be a time-lag type.

Motor drive precharge

Precharging a 400 V DC link of 1,000 µF through a 10 Ω resistor starts at 40 A, takes 50 ms (5τ) and puts 80 J into the resistor.

Transformer breakers

A 1,000 kVA, 480 V transformer listed at 4.2× has 1,203 A full-load current and draws about 5,052 A on energising, which the breaker must carry for 0.01 s.

Generator and starter sizing

A 100 hp, 460 V code G motor needs 560 to 629 kVA at standstill and 702.9 to 789.5 A of locked-rotor current, far more than its running load.

Hot-plugging boards

Plugging a board with 2,200 µF into a 12 V rail through 50 mΩ peaks at 240 A for about 0.55 ms, which is why hot-swap controllers exist.

Last updated: