Motor Full-Load Amps (FLA) Calculator
Calculate full-load amps (FLA) from motor horsepower or kilowatts, line voltage, phase (single or three), power factor, and efficiency. Returns input kW, shaft kW, and apparent power (kVA) for conductor and overload sizing.
How to Use
- Enter the motor's rated output power (HP for US, kW for metric nameplates).
- Set line-to-line voltage — 120 V / 240 V single-phase for fractional-HP; 208 V / 480 V three-phase for industrial.
- Select phase: single-phase for residential and fractional motors, three-phase for most commercial/industrial motors.
- Enter rated power factor (typical 0.80–0.90) and efficiency (typical 0.85–0.95) from the nameplate.
- Results: full-load amps, electrical input kW, shaft output kW, and apparent kVA.
Worked Example
A 10 HP conveyor motor on 460 V three-phase, PF 0.85, efficiency 90%. Shaft power = 10 × 746 = 7,460 W. Input power = 7,460 ÷ 0.90 = 8,289 W. Current = 8,289 ÷ (√3 × 460 × 0.85) = 8,289 ÷ 677.2 = 12.2 A. Apparent power = 8,289 ÷ 0.85 = 9.75 kVA.
For a US installation, the conductors are sized from NEC Table 430.250, which lists 14 A for 10 HP at 460 V, so they need 125% × 14 = 17.5 A of ampacity (NEC 430.22). The overload relay is set from the nameplate current instead, at up to 125% of it (NEC 430.32).
The common mistake: leaving out √3. 8,289 ÷ (460 × 0.85) gives 21.2 A, which is the single-phase formula applied to a three-phase motor and overstates the current by 73%.
Show Work
Formulas
History of Motor Current Specification
Michael Faraday built the first electric motor in 1821 — a wire carrying current swung in circles around a magnet submerged in mercury. The first practical DC motor (Davenport, 1834) and AC induction motor (Tesla and Ferraris independently, 1887–1888) followed. By 1890 the National Electric Light Association was already publishing conductor-sizing recommendations for motor circuits.
The US National Electrical Code (NEC) was first published in 1897 by the National Fire Protection Association, and Article 430 (Motors, Motor Circuits, and Controllers) has existed in substantially its current form since the 1920s. The tabulated full-load currents in NEC Tables 430.250 (three-phase) and 430.248 (single-phase) were developed to give electricians standardized values for conductor sizing regardless of specific motor nameplate variations — a fundamentally conservative approach that sometimes exceeds actual nameplate FLA by 10–20%.
Modern motor-efficiency standards (NEMA MG-1 Premium in the US, IE3/IE4 in Europe) have tightened the efficiency floor significantly since 1990. A typical 10 HP three-phase motor in 1990 ran at ~87% efficiency; the same motor today is ~93%. The FLA calculation hasn't changed, but modern motors draw less input current per unit of shaft power because they waste less as heat.
About This Calculator
Enter motor rated HP or kW, line voltage, phase count, power factor, and efficiency. The calculator returns full-load line current (FLA), input kW demand, shaft output kW, and apparent power (kVA) — all the numbers you need for branch-circuit sizing, VFD selection, or transformer loading.
Important: for US NEC-compliant conductor sizing, cross-check calculated FLA against NEC Tables 430.248/430.250 and use the table values for anything code-referenced. The calculated value is for analytical work and non-US standards. Everything runs client-side; no nameplate data leaves your browser.
Frequently Asked Questions
NEC table vs. calculated FLA — which to use?
In the US, NEC 430.6(A) splits it: conductors, disconnects and short-circuit protection are sized from the table currents (Table 430.248 single-phase, 430.250 three-phase), not the nameplate; overload protection is set from the motor's nameplate current (430.32). The table values are deliberately conservative — for a 10 HP, 460 V motor the table says 14 A where this formula gives 12.2 A. Use the calculated value to understand the load, check a nameplate, or work outside the NEC.
Why is motor FLA different from "watts divided by voltage"?
Motors have both power factor (reactive losses) and efficiency (mechanical losses). The nameplate HP is output shaft power. Input electrical power = shaft power / efficiency; input current = input power / (V × PF). Skipping either factor underestimates current by 20–40%.
HP vs. kW — exact conversion?
1 mechanical horsepower is 745.7 W; US motor practice rounds it to 746 W, and this calculator uses 746 W. The 0.04% difference never changes a sizing decision. Rule of thumb: kW ≈ HP × 0.75.
Do efficiency and PF vary with load?
Yes — both drop off significantly below 50% load. Nameplate PF and η are at rated load; an oversized motor running at 25% load has much lower PF (~0.5) and efficiency (~80%), which means higher current draw per output watt. Right-size motors for energy efficiency.
What changes for VFD-driven motors?
Variable-frequency drives can shift the effective current. At reduced speeds, cooling drops (if fan-cooled from the shaft), so continuous duty current may need to be derated below FLA. Modern inverter-duty motors use separate cooling fans to maintain torque at low speeds.
How do I use the Motor Full-Load Amps (FLA) Calculator?
Just type your numbers. The answer shows up right away — there is no button to press. Change anything and it updates by itself.
Does it cost anything or need an account?
No. The tool is completely free, there is no account to create, and it keeps working offline after the page first loads.
Is anything I type uploaded?
No. The tool works entirely on your device, so the values you enter never leave your browser.
Common Use Cases
Conductor Sizing per NEC 430
A 10 HP, 460 V three-phase motor calculates to 12.2 A, but conductors are sized from NEC Table 430.250: 14 A. NEC 430.22 asks for 125% of that, so the branch-circuit conductors need at least 17.5 A of ampacity.
VFD Selection
A 5 HP, 480 V motor calculates to 5.9 A (the NEC table lists 7.6 A at 460 V). Pick a drive by its continuous output current against the motor nameplate current, not by horsepower alone.
Generator Sizing
A 25 HP three-phase motor at PF 0.85 and 90% efficiency needs 24.4 kVA running. Starting across the line takes several times that, so size the generator with its maker’s motor-starting data, not the running kVA alone.
Transformer Loading
Add the kVA of every motor, not the horsepower: three 10 HP motors at PF 0.85 and 90% efficiency are 3 × 9.75 = 29.3 kVA, comfortably inside a 45 kVA transformer.
Energy Cost Estimation
15 HP motor running 8 hours/day at 85% load: input = (15 × 0.746 × 0.85) / 0.9 ≈ 10.6 kW. At $0.12/kWh × 8 × 250 working days = ~$2,500/year energy cost.
Last updated: