Power Factor Calculator

Find the power factor from volts, amps and watts, convert between kVA, kW and kvar, and size the capacitors that raise a load’s power factor to a target, in kvar and microfarads for single-phase and three-phase supplies.

Calculator Electronics Updated Oct 5, 2026
How to Use
  1. Pick a tab. Power factor works out PF from meter readings, kVA ↔ kW converts between the sides of the power triangle, and Correction sizes capacitors.
  2. Power factor: choose single- or three-phase and enter the voltage, the current and the real power from a wattmeter or power analyser.
  3. kVA ↔ kW: choose what to find and enter the other two (for example kVA and PF to get kW, or kW and kvar to get the PF).
  4. Correction: enter the load’s kW, its present and target power factor, the supply voltage and frequency. The result is the capacitor kvar and the capacitance per phase for a delta or star bank.
  5. Read the highlighted answer and the readouts, use a preset for a worked example, and check Show Work for every step.
Input
cos φ, 0 to 1
cos φ1
cos φ2
Presets
Power Triangle
Power factor
—
Phase angle
—
Apparent power
—
Reactive power
—

Worked Example

Power factor from a meter. A 240 V load draws 10 A and a wattmeter reads 2,000 W. The apparent power is 240 × 10 = 2,400 VA, so PF = 2,000 ÷ 2,400 = 0.8333. The phase angle is arccos 0.8333 = 33.56°, and the reactive power is √(2,400² − 2,000²) = 1,327 var.

kVA to kW. A 100 kVA generator feeding a load at PF 0.8 can deliver 100 × 0.8 = 80 kW; the other side of the triangle is 100 × 0.6 = 60 kvar.

Correction capacitors. A 100 kW, 480 V, 60 Hz three-phase load runs at PF 0.75 and should run at 0.95. tan(arccos 0.75) = 0.8819 and tan(arccos 0.95) = 0.3287, so Qc = 100 × (0.8819 − 0.3287) = 55.32 kvar. In a delta bank each capacitor is 55,320 ÷ (3 × 2π × 60 × 480²) = 212.3 µF. The line current falls from 160.4 A to 126.6 A.

The common mistake: subtracting the kVA. Before correction the load takes 100 ÷ 0.75 = 133.3 kVA, after it 100 ÷ 0.95 = 105.3 kVA. The difference, 28.07, looks like the bank size but is only half of it. The capacitors have to cancel reactive power, the vertical side of the triangle, which falls from 88.19 to 32.87 kvar: 55.32 kvar.

Show Work

Enter values and calculate to see the step-by-step breakdown.

Formulas

Power factor
PF = P ÷ S = cos φ
S = V × I single-phase, √3 × VLL × I three-phase
kVA to kW
kW = kVA × PF
And kVA = kW ÷ PF
Power triangle
S² = P² + Q²
Q = √(S² − P²) = P × tan φ
Correction kvar
Qc = P × (tan φ1 − tan φ2)
Same for single-phase and three-phase (ABB formula 2.1)
Delta bank
C = Qc ÷ (3 × ω × VLL²)
Each of the three capacitors; ω = 2πf
Star bank
C = Qc ÷ (ω × VLL²)
Three times the delta capacitance, at a third of the voltage stress
Single-phase capacitor
C = Qc ÷ (ω × V²)
Capacitor current I = Qc ÷ V

Where Power Factor Comes From

In an AC circuit with inductance or capacitance the current is shifted in time from the voltage, so part of it carries no net energy. Charles Proteus Steinmetz gave engineers the tool to handle this in his 1893 paper Complex Quantities and Their Use in Electrical Engineering, which treated voltages and currents as complex numbers. Power splits into a real part that does work and a reactive part that flows back and forth, the two sides of the power triangle, and the power factor is the cosine of the angle between them.

Low power factor costs money because every conductor, transformer and generator is loaded by the full current. ABB’s Technical Application Paper No. 8 sets out how suppliers recover that cost. Tariffs typically charge for reactive energy when the monthly average power factor is between 0.7 and 0.9 and nothing above 0.9. Below 0.7 the supplier can require correction. A power factor of 0.9 means drawing no more reactive energy than half the active energy (tan φ ≤ 0.5). ABB stresses that contracts differ from country to country.

The fix is local reactive power from capacitors. ABB’s guide gives Qc = P × (tan φ1 − tan φ2) for single-phase and three-phase alike, a K-factor table built from the same formula (0.398 kvar per kW from 0.75 to 0.90), and the capacitance of delta and star banks. Its low-voltage capacitors use metallised polypropylene film, which is self-healing: a breakdown vaporises the thin metal around the fault and isolates it. Modern loads add a second issue. A rectifier input draws current in pulses, so its true power factor also depends on harmonic distortion, which capacitors cannot fix and which can resonate with them. ABB covers this with harmonic filters.

About This Calculator

This calculator brings together the three power factor jobs. It reads a power factor from voltage, current and wattmeter readings on single-phase or three-phase supplies. It converts between kVA, kW, kvar and PF in any direction. And it sizes correction capacitors in kvar and in microfarads per capacitor for single-phase, delta and star connections, showing how much apparent power and line current the correction saves. Every result is drawn on the power triangle.

It works with displacement power factor on sinusoidal supplies, which is what the capacitor formulas assume. On sites with many drives or rectifiers, measure the true power factor and harmonics before choosing a bank. Everything runs in your browser; nothing you enter is sent anywhere.

Related tools: Inrush Current Calculator, Transformer Efficiency Calculator, and Power Calculator.

Frequently Asked Questions

How do you calculate power factor?

Divide the real power by the apparent power: PF = P ÷ (V × I). A 240 V load drawing 10 A and 2,000 W has S = 2,400 VA, so PF = 2,000 ÷ 2,400 = 0.8333. The phase angle is arccos 0.8333 = 33.56° and the reactive power is √(2,400² − 2,000²) = 1,327 var. For three-phase use S = √3 × V × I.

How do I convert kVA to kW?

Multiply by the power factor: kW = kVA × PF. A 100 kVA generator at PF 0.8 can deliver 80 kW, with 60 kvar of reactive power. Going the other way, kVA = kW ÷ PF, so a 50 kW load at PF 0.8 needs 62.5 kVA of supply.

How much capacitor kvar do I need to correct the power factor?

Qc = P × (tan φ1 − tan φ2), where φ1 and φ2 are the angles before and after; ABB’s guide notes it holds for single-phase and three-phase alike. A 100 kW load at PF 0.75 has tan φ1 = 0.8819; at 0.95, tan φ2 = 0.3287, so Qc = 100 × 0.5532 = 55.32 kvar. ABB’s own example, 300 kW from 0.75 to 0.90, needs 119.3 kvar.

How do I convert kvar to microfarads?

Divide by ωV², where ω = 2πf. In a three-phase delta bank each capacitor sees the line voltage, so C = Qc ÷ (3ωV²): 55.32 kvar at 480 V and 60 Hz is 212.3 µF per capacitor. A star bank needs three times that, 636.9 µF each. Single-phase: C = Qc ÷ (ωV²), so 1.383 kvar at 230 V and 50 Hz is 83.22 µF.

Why not correct the power factor all the way to 1?

The last few hundredths cost the most. Taking 100 kW from PF 0.75 to 1 needs 88.19 kvar against 55.32 kvar for 0.95, 59 % more capacitors for little extra saving. A fixed bank sized for unity also turns the power factor leading when the load drops. ABB notes that tariffs typically charge for reactive energy only below a monthly average PF of 0.9.

How do I use the Power Factor Calculator?

Just type your numbers. The answer shows up right away — there is no button to press. Change anything and it updates by itself.

Is it free? Does it work without internet?

Yes to both. It is free with no sign-up, and once the page has loaded it keeps working even with no internet.

Where does my data go?

Nowhere — every calculation runs on your own device. Nothing you enter is uploaded, logged, or stored.

Common Use Cases

Avoiding reactive power charges

A 300 kW plant at PF 0.75 needs a 119.3 kvar bank to reach 0.90, the level below which ABB says tariffs typically start charging for reactive energy.

Freeing cable and transformer capacity

Correcting 300 kW at 400 V from PF 0.8 to 0.93 with 106.4 kvar cuts the line current from 541.3 A to 465.6 A, 14 % less.

Generator ratings

A 100 kVA generator at PF 0.8 gives 80 kW; a 50 kW load at PF 0.8 needs a 62.5 kVA supply.

Checking a meter reading

A 480 V three-phase motor drawing 14 A and 9.9 kW runs at PF 0.8506. Reaching 0.95 would take 2.867 kvar.

Single-phase motor capacitor

A 2 kW, 230 V, 50 Hz motor at PF 0.7 needs 83.22 µF (1.383 kvar) to reach 0.95, which drops its supply current from 12.42 A to 9.153 A.

Last updated: