Voltage Drop Calculator
Calculate DC or single-phase AC voltage drop across a run of copper wire. Input current, cable length, and AWG; returns drop in volts, percent, the voltage left at the load, and power lost as heat.
How to Use
- Enter the current in amps the load draws when running (steady state, not inrush).
- Enter the one-way length of the cable run, with a unit (25ft, 7.5m). The calculator doubles it for the return path.
- Pick the wire gauge (AWG). Common values: 14 AWG for 15 A household circuits, 12 AWG for 20 A, 10 AWG for 30 A.
- Enter the supply voltage (12 V DC, 48 V DC, 120 or 240 V AC). The percent drop is relative to this value.
- Read the drop, the voltage left at the load and the watts lost in the wire; if the drop is over 3%, try the next gauge up.
Worked Example
A 12 V LED strip draws 10 A at the end of a 25 ft run of 12 AWG copper. The current goes out and comes back, so there are 50 ft (15.24 m) of wire. 12 AWG is 5.21 Ω per km, so R = 5.21 × 0.01524 = 0.0794 Ω, and the drop is 10 A × 0.0794 Ω = 0.79 V, 6.6% of 12 V. The strip gets 11.21 V, and the wire turns 0.79 × 10 = 7.9 W into heat.
The fix: a bigger wire. 10 AWG drops 0.50 V (4.2%); 8 AWG drops 0.31 V (2.6%), inside the 3% guideline. Each two sizes up cuts the drop by about 37%.
The common mistake: forgetting the return path. Using the 25 ft one-way length gives 0.40 V, exactly half the real drop, and a 12 AWG run that looks fine on paper.
Show Work
Formulas
History of Voltage Drop
The "War of the Currents" of the late 1880s, between Edison's direct-current distribution and the Westinghouse and Tesla alternating-current system, turned largely on voltage drop. Edison's low-voltage DC stations could not serve customers much more than a mile away: wire resistance forced either massive copper cables or unacceptable losses at the customer end. AC could be stepped up to a high voltage for transmission (low current, so low I²R loss) and stepped back down locally, and the transformer made long-distance distribution practical.
American Wire Gauge, the sizing system this calculator uses, has been used since 1857, when it was set out by the Brown & Sharpe company. Its spacing is logarithmic: every 3 gauges doubles the cross-section and halves the resistance, and every 6 gauges doubles the diameter. The National Electrical Code was first published in 1897 and has been sponsored by the National Fire Protection Association since 1911; its 3% and 5% voltage-drop figures appear as informational notes rather than requirements.
About This Calculator
Reference: Wire Gauge Table.
Enter the running current, the one-way cable length, the wire gauge and the supply voltage; the calculator returns the voltage drop, the percent drop relative to the supply, the voltage actually delivered to the load, and the power lost as heat along the run. The round-trip doubling is automatic: enter the physical distance, not the total conductor length.
Resistances are for solid annealed copper at 20 °C (for example, 5.21 Ω per km for 12 AWG). Wire at its 75 °C rating has about 22% more resistance, and aluminum about 60% more. All math runs in your browser; nothing is sent to a server.
Frequently Asked Questions
Why do I double the length?
Current flows from source to load and back again, so one foot of cable run means two feet of conductor. If you enter only the one-way length and forget the factor of two, your drop comes out half the true value. This calculator does the doubling for you.
What drop is acceptable?
Informational notes in the US National Electrical Code (NEC) suggest no more than 3% on a branch circuit and 5% for feeder plus branch together. They are advice rather than enforceable rules, but they are the usual design target. Low-voltage DC systems need the same percentage: on 12 V, 3% is only 0.36 V.
Copper vs. aluminum?
Aluminum has about 61% of copper's conductivity, so the same AWG size in aluminum has roughly 1.6 times the resistance and 1.6 times the drop. To match copper you go up about two sizes (6 AWG copper is close to 4 AWG aluminum). This calculator uses copper; multiply the drop by 1.6 for aluminum.
AC vs. DC drop: are they the same?
For household AC at typical distances, the wiring's reactance is small, so the DC resistance formula is within a few percent of the true AC drop. For long runs, large conductors, high currents or steel conduit, add the reactance using the effective-impedance values in NEC Chapter 9, Table 9.
Does wire temperature matter?
Yes. This calculator uses copper resistance at 20 °C. Copper's resistance rises about 0.4% per °C, so a conductor running at its 75 °C rating has about 22% more resistance and 22% more drop. For a fully loaded circuit, the NEC Chapter 9, Table 8 values (given at 75 °C) are the conservative choice.
How do I use the Voltage Drop Calculator?
Just type your numbers. The answer shows up right away — there is no button to press. Change anything and it updates by itself.
Is it free? Does it work without internet?
Yes to both. It is free with no sign-up, and once the page has loaded it keeps working even with no internet.
Where does my data go?
Nowhere — every calculation runs on your own device. Nothing you enter is uploaded, logged, or stored.
Common Use Cases
12 V LED Strip Runs
A 10 A LED strip at the end of 50 ft of 14 AWG drops 2.5 V, 21% of 12 V, and the far end visibly dims. Even 10 AWG still drops 1.0 V (8.3%), which is why long 12 V strips are fed from both ends or from the middle.
48 V Solar Array Wiring
30 A from a 48 V array over 30 ft of 10 AWG drops 1.8 V (3.75%) and turns 54 W into heat. Going up to 8 AWG brings it to 1.1 V (2.35%) and saves about 20 W while the sun is up.
RV and Automotive 12 V Accessories
An inverter drawing 15 A through 20 ft of 14 AWG loses 1.5 V (12.6%), enough to trip its low-voltage alarm. 8 AWG holds the drop to 0.38 V (3.1%).
Garage Sub-Panel Feeder
A 50 A sub-panel 80 ft from the main on 6 AWG copper at 240 V drops 3.2 V, 1.3%, well inside the 3% guideline with no upsizing needed.
Trolling Motor Battery Cable
A 60 A trolling motor on 20 ft of 4 AWG loses 0.6 V (5%) from a 12 V battery. 6 AWG would lose 0.95 V (7.9%) and noticeably cut thrust.
Last updated: