NEMA Plug & Receptacle Chart

Every NEMA plug and receptacle configuration with its face drawn, voltage, amps and wiring. Look one up or identify an outlet from its blades.

Reference Electronics Updated Oct 5, 2026
Learn how this works
How to Use
  1. Pick a configuration from the list, or press a preset such as the 14-50 range and EV outlet or the TT-30 RV outlet.
  2. Compare the receptacle drawing with the outlet on your wall, or the plug drawing with the blades on your cord. G is the ground pin, W the neutral, X, Y and Z the hot contacts.
  3. Read the voltage, current and poles-and-wires readouts, then the Show Work steps that explain how the name follows from the blades.
  4. Don’t know the name? Switch to Identify and answer what you can see: straight or twist-lock blades, how many contacts, whether there is a ground pin, and the breaker rating.
  5. Scroll to the full chart below to see every configuration side by side; click a name to load it.
Input
volts, amps, poles / wires
count the ground pin too
U-shaped, round or hooked
V, if marked or measured
A, from the breaker or marking
Presets
Receptacle and Plug Faces
NEMA
—
Voltage
—
Current
—
Poles / wires
—

Worked Example

A range outlet. The receptacle behind a range has four straight contacts: a U-shaped ground pin at the top, two vertical hot slots (X and Y) and a straight vertical neutral slot (W) at the bottom. Four contacts with a ground pin means 3-pole 4-wire grounding; with a 50 A breaker that is a NEMA 14-50R, rated 125/250 V. At its full rating on a 240 V supply it carries 240 × 50 = 12,000 W. An EV charger, a continuous load, is set to 50 ÷ 1.25 = 40 A, which is 9,600 W.

A dryer outlet. The same layout with an L-shaped neutral slot is the 30 A version, the 14-30R: 240 × 30 = 7,200 W. If the outlet has only three contacts (two angled hots and an L-shaped neutral at the top, no ground pin), it is the older 10-30R, which has not been allowed on new branch circuits since the 1996 National Electrical Code.

The common mistake: treating every “30 amp” outlet as the same. An RV’s 30 A plug is a TT-30P: 125 V, one hot, a neutral and a ground, 120 × 30 = 3,600 W. The 10-30 and 14-30 dryer outlets are also 30 A but 125/250 V, with 240 V between their hot contacts. Wiring a TT-30R from a 2-pole breaker, or forcing an adapter onto a dryer outlet, can put 240 V into a 120 V RV instead of 120 V. Check the face, not just the amp rating.

Show Work

Pick a configuration to see how its name follows from the blades.

Ratings Explained

The name
[L] family − amps [R|P]
L = locking. Family (the number before the dash) = voltage and poles/wires. After the dash = current rating in amps. R = receptacle, P = plug.
Poles and wires
wires = poles + 1 (grounding)
Poles carry current (hots and neutral). A grounding device adds one wire for the ground pin, which is not a pole: 14-50 is 3-pole 4-wire.
Contact letters
G ground · W neutral · X Y Z hot
The letters printed beside the terminals on the charts. The neutral is the white conductor; the ground is green or bare.
Single-phase power
P = V × I
At the full rating: 5-15 on 120 V = 1,800 W; 14-50 on 240 V = 12,000 W.
Three-phase power
S = √3 × VLL × I
L21-30 on a 120/208 V wye supply: √3 × 208 × 30 = 10,808 VA.
Continuous load
Imax = rating ÷ 1.25
A load running for hours (EV charging) needs a circuit rated 125 % of it: 50 A → 40 A, 30 A → 24 A, 20 A → 16 A.

NEMA Configuration Chart

All 112 configurations in the ANSI/NEMA WD 6-1997 straight-blade, locking and travel-trailer pages: 45 straight-blade and 67 locking. Receptacle faces are drawn from the front; a plug is the mirror image. The 24 locking ratings marked “not on maker charts” (50 A and 60 A twist-locks) appear in WD 6 but not on the Hubbell, Bryant or Qualtek charts, so their faces are not drawn. Click a name to load it in the tool.

Straight-blade devices

Receptacle faceNEMAVoltage (V)Current (A)PhasePoles / wiresGround pinMade as
1-15125151-phase2P 2WNo1-15R, 1-15P
1-20125201-phase2P 2WNoPlug only (mates with 5-20R)
1-30125301-phase2P 2WNoPlug only (mates with 5-30R)
2-15250151-phase2P 2WNoPlug only (mates with 6-15R)
2-20250201-phase2P 2WNo2-20R, 2-20P
2-30250301-phase2P 2WNo2-30R, 2-30P
5-15125151-phase2P 3WYes5-15R, 5-15P
5-20125201-phase2P 3WYes5-20R, 5-20P
5-30125301-phase2P 3WYes5-30R, 5-30P
5-50125501-phase2P 3WYes5-50R, 5-50P
6-15250151-phase2P 3WYes6-15R, 6-15P
6-20250201-phase2P 3WYes6-20R, 6-20P
6-30250301-phase2P 3WYes6-30R, 6-30P
6-50250501-phase2P 3WYes6-50R, 6-50P
7-15277 AC151-phase2P 3WYes7-15R, 7-15P
7-20277 AC201-phase2P 3WYes7-20R, 7-20P
7-30277 AC301-phase2P 3WYes7-30R, 7-30P
7-50277 AC501-phase2P 3WYes7-50R, 7-50P
24-15347 AC151-phase2P 3WYes24-15R, 24-15P
24-20347 AC201-phase2P 3WYes24-20R, 24-20P
24-30347 AC301-phase2P 3WYes24-30R, 24-30P
24-50347 AC501-phase2P 3WYes24-50R, 24-50P
10-20125/250201-phase3P 3WNo10-20R, 10-20P
10-30125/250301-phase3P 3WNo10-30R, 10-30P
10-50125/250501-phase3P 3WNo10-50R, 10-50P
11-153Ø 250153-phase3P 3WNo11-15R, 11-15P
11-203Ø 250203-phase3P 3WNo11-20R, 11-20P
11-303Ø 250303-phase3P 3WNo11-30R, 11-30P
11-503Ø 250503-phase3P 3WNo11-50R, 11-50P
14-15125/250151-phase3P 4WYes14-15R, 14-15P
14-20125/250201-phase3P 4WYes14-20R, 14-20P
14-30125/250301-phase3P 4WYes14-30R, 14-30P
14-50125/250501-phase3P 4WYes14-50R, 14-50P
14-60125/250601-phase3P 4WYes14-60R, 14-60P
15-153Ø 250153-phase3P 4WYes15-15R, 15-15P
15-203Ø 250203-phase3P 4WYes15-20R, 15-20P
15-303Ø 250303-phase3P 4WYes15-30R, 15-30P
15-503Ø 250503-phase3P 4WYes15-50R, 15-50P
15-603Ø 250603-phase3P 4WYes15-60R, 15-60P
18-153ØY 120/208153-phase4P 4WNo18-15R, 18-15P
18-203ØY 120/208203-phase4P 4WNo18-20R, 18-20P
18-303ØY 120/208303-phase4P 4WNo18-30R, 18-30P
18-503ØY 120/208503-phase4P 4WNo18-50R, 18-50P
18-603ØY 120/208603-phase4P 4WNo18-60R, 18-60P
TT-30125301-phase2P 3WYesTT-30R, TT-30P

Locking (twist-lock) devices

Receptacle faceNEMAVoltage (V)Current (A)PhasePoles / wiresGround pinMade as
L1-15125151-phase2P 2WNoL1-15R, L1-15P
L2-20250201-phase2P 2WNoL2-20R, L2-20P
L5-15125151-phase2P 3WYesL5-15R, L5-15P
L5-20125201-phase2P 3WYesL5-20R, L5-20P
L5-30125301-phase2P 3WYesL5-30R, L5-30P
—L5-50125501-phase2P 3WYesL5-50R, L5-50P — in WD 6; not on maker charts
—L5-60125601-phase2P 3WYesL5-60R, L5-60P — in WD 6; not on maker charts
L6-15250151-phase2P 3WYesL6-15R, L6-15P
L6-20250201-phase2P 3WYesL6-20R, L6-20P
L6-30250301-phase2P 3WYesL6-30R, L6-30P
—L6-50250501-phase2P 3WYesL6-50R, L6-50P — in WD 6; not on maker charts
—L6-60250601-phase2P 3WYesL6-60R, L6-60P — in WD 6; not on maker charts
L7-15277 AC151-phase2P 3WYesL7-15R, L7-15P
L7-20277 AC201-phase2P 3WYesL7-20R, L7-20P
L7-30277 AC301-phase2P 3WYesL7-30R, L7-30P
—L7-50277 AC501-phase2P 3WYesL7-50R, L7-50P — in WD 6; not on maker charts
—L7-60277 AC601-phase2P 3WYesL7-60R, L7-60P — in WD 6; not on maker charts
—L24-20347 AC201-phase2P 3WYesL24-20R, L24-20P
L8-20480 AC201-phase2P 3WYesL8-20R, L8-20P
L8-30480 AC301-phase2P 3WYesL8-30R, L8-30P
—L8-50480 AC501-phase2P 3WYesL8-50R, L8-50P — in WD 6; not on maker charts
—L8-60480 AC601-phase2P 3WYesL8-60R, L8-60P — in WD 6; not on maker charts
L9-20600 AC201-phase2P 3WYesL9-20R, L9-20P
L9-30600 AC301-phase2P 3WYesL9-30R, L9-30P
—L9-50600 AC501-phase2P 3WYesL9-50R, L9-50P — in WD 6; not on maker charts
—L9-60600 AC601-phase2P 3WYesL9-60R, L9-60P — in WD 6; not on maker charts
L10-20125/250201-phase3P 3WNoL10-20R, L10-20P
L10-30125/250301-phase3P 3WNoL10-30R, L10-30P
L11-153Ø 250153-phase3P 3WNoL11-15R, L11-15P
L11-203Ø 250203-phase3P 3WNoL11-20R, L11-20P
L11-303Ø 250303-phase3P 3WNoL11-30R, L11-30P
L12-203Ø 480203-phase3P 3WNoL12-20R, L12-20P
L12-303Ø 480303-phase3P 3WNoL12-30R, L12-30P
L13-303Ø 600303-phase3P 3WNoL13-30R, L13-30P
L14-20125/250201-phase3P 4WYesL14-20R, L14-20P
L14-30125/250301-phase3P 4WYesL14-30R, L14-30P
—L14-50125/250501-phase3P 4WYesL14-50R, L14-50P — in WD 6; not on maker charts
—L14-60125/250601-phase3P 4WYesL14-60R, L14-60P — in WD 6; not on maker charts
L15-203Ø 250203-phase3P 4WYesL15-20R, L15-20P
L15-303Ø 250303-phase3P 4WYesL15-30R, L15-30P
—L15-503Ø 250503-phase3P 4WYesL15-50R, L15-50P — in WD 6; not on maker charts
—L15-603Ø 250603-phase3P 4WYesL15-60R, L15-60P — in WD 6; not on maker charts
L16-203Ø 480203-phase3P 4WYesL16-20R, L16-20P
L16-303Ø 480303-phase3P 4WYesL16-30R, L16-30P
—L16-503Ø 480503-phase3P 4WYesL16-50R, L16-50P — in WD 6; not on maker charts
—L16-603Ø 480603-phase3P 4WYesL16-60R, L16-60P — in WD 6; not on maker charts
L17-303Ø 600303-phase3P 4WYesL17-30R, L17-30P
—L17-503Ø 600503-phase3P 4WYesL17-50R, L17-50P — in WD 6; not on maker charts
—L17-603Ø 600603-phase3P 4WYesL17-60R, L17-60P — in WD 6; not on maker charts
L18-203ØY 120/208203-phase4P 4WNoL18-20R, L18-20P
L18-303ØY 120/208303-phase4P 4WNoL18-30R, L18-30P
L19-203ØY 277/480203-phase4P 4WNoL19-20R, L19-20P
L19-303ØY 277/480303-phase4P 4WNoL19-30R, L19-30P
L20-203ØY 347/600203-phase4P 4WNoL20-20R, L20-20P
L20-303ØY 347/600303-phase4P 4WNoL20-30R, L20-30P
L21-203ØY 120/208203-phase4P 5WYesL21-20R, L21-20P
L21-303ØY 120/208303-phase4P 5WYesL21-30R, L21-30P
—L21-503ØY 120/208503-phase4P 5WYesL21-50R, L21-50P — in WD 6; not on maker charts
—L21-603ØY 120/208603-phase4P 5WYesL21-60R, L21-60P — in WD 6; not on maker charts
L22-203ØY 277/480203-phase4P 5WYesL22-20R, L22-20P
L22-303ØY 277/480303-phase4P 5WYesL22-30R, L22-30P
—L22-503ØY 277/480503-phase4P 5WYesL22-50R, L22-50P — in WD 6; not on maker charts
—L22-603ØY 277/480603-phase4P 5WYesL22-60R, L22-60P — in WD 6; not on maker charts
L23-203ØY 347/600203-phase4P 5WYesL23-20R, L23-20P
L23-303ØY 347/600303-phase4P 5WYesL23-30R, L23-30P
—L23-503ØY 347/600503-phase4P 5WYesL23-50R, L23-50P — in WD 6; not on maker charts
—L23-603ØY 347/600603-phase4P 5WYesL23-60R, L23-60P — in WD 6; not on maker charts

Background: Where the Configurations Come From

The configurations are set by the National Electrical Manufacturers Association standard ANSI/NEMA WD 6 for wiring devices. Its configuration pages (pp. 141–144 in the 1997 edition) are a grid: rows are voltage and pole/wire arrangements, columns are 15, 20, 30, 50 and 60 A, and blank cells are “reserved for future configurations”. That grid is why the numbering skips: straight-blade numbers 3, 4, 8, 9, 12, 13, 16, 17 and 19 to 23 are reserved rows with no straight-blade device, while the locking series uses almost all of them.

Each configuration is keyed: blade widths, angles and spacing differ so that a plug fits only a receptacle of its own configuration. The deliberate exceptions are the T-shaped slots on 5-20R and 6-20R, which accept 15 A plugs, and three plug-only devices: the non-grounding 1-20P and 1-30P fit 5-20R and 5-30R receptacles, and the 2-15P fits a 6-15R.

The TT-30 is not part of the numbered grid. WD 6 lists it on its “specific purpose” page as the travel-trailer configuration, 120 V AC 2-pole 3-wire grounding, alongside the midget-locking ML1–ML3, the FSL configurations (28 V DC and 400 Hz) and the SS1/SS2 marine ship-to-shore connectors. The 1996 National Electrical Code ended the 3-wire 10-30 and 10-50 for new dryer and range circuits; existing ones may stay.

Sources

WD 6 itself is sold by NEMA. Every configuration here (number, voltage, amps, phase, poles and wires, grounding) was checked against the WD 6-1997 configuration pages and the manufacturer charts below; Leviton’s and Eaton’s charts could not be downloaded. Uses are only given where an installation guide or manual names the configuration.

About This Tool

Reference: World Plug & Socket Types.

This chart draws every NEMA receptacle and plug face from one verified dataset, the same one the NEMA plug types explained article prints its tables from, so the two cannot disagree. Look up a configuration by name, or work backwards from what you can see on an outlet: blade shape, number of contacts, ground pin, voltage and breaker rating.

It identifies connectors; it does not size circuits. Breaker rating, wire gauge and grounding have to match the receptacle, and an outlet is only as correct as the wiring behind it, so check unfamiliar outlets with a meter or tester and use a licensed electrician for new circuits. Everything runs in your browser.

Related tools: Wire Gauge Reference, Voltage Drop Calculator, and AC Power Calculator.

Frequently Asked Questions

How do I read a NEMA designation like 14-50R or L14-30P?

The number before the dash is the configuration family, which fixes the voltage and the number of poles and wires: 5 is 125 V 2-pole 3-wire grounding, 6 is 250 V, and 14 is 125/250 V 3-pole 4-wire grounding. The number after the dash is the current rating in amps. A leading L means a locking (twist-lock) device, and a trailing R or P means receptacle or plug. So L14-30P is a 125/250 V, 30 A, 3-pole 4-wire locking plug.

What is the difference between a 10-30 and a 14-30 dryer outlet?

Both are 125/250 V, 30 A. The 10-30 is 3-pole 3-wire with no separate ground: the dryer frame is grounded through the neutral. The 14-30 is 3-pole 4-wire with a separate ground pin. Whirlpool’s installation instructions state that the National Electrical Code has required the 4-wire connection for new branch circuits since 1996, so a 10-30 is only found on older circuits.

Is a TT-30 RV outlet 120 V or 240 V?

A TT-30 is 125 V, 30 A, 2-pole 3-wire grounding: one hot, one neutral and a ground, which supplies 120 V × 30 A = 3,600 W. It looks a little like the 125/250 V 10-30, which is why wiring a TT-30R from a 2-pole 240 V breaker can damage an RV. The 50 A RV outlet is a 14-50 (125/250 V).

How much can I draw from a 14-50 for an EV charger?

A 14-50 is rated 50 A. Because EV charging is a continuous load, the circuit must be rated 125 % of the load, so the charger is set to 50 ÷ 1.25 = 40 A. ChargePoint’s Home Flex installation guide lists exactly that: a 50 A circuit gives a 40 A maximum load. At 240 V that is 9,600 W.

Why does my 20 A outlet have a T-shaped slot?

On a 5-20R or 6-20R one slot is T-shaped, so it accepts both the 15 A plug (5-15P or 6-15P) and the 20 A plug, whose blade is turned 90°. A 20 A plug therefore cannot go into a 15 A receptacle, which has no T-slot.

How do I use the NEMA Plug & Receptacle Chart?

Just type your numbers. The answer shows up right away — there is no button to press. Change anything and it updates by itself.

Is it free? Does it work without internet?

Yes to both. It is free with no sign-up, and once the page has loaded it keeps working even with no internet.

Where does my data go?

Nowhere — every calculation runs on your own device. Nothing you enter is uploaded, logged, or stored.

Common Use Cases

Identify a wall outlet

Four straight contacts with a ground pin and a 30 A breaker narrows 112 configurations to two: the 14-30 (125/250 V) and the 15-30 (3-phase 250 V). The voltage settles it.

Buy the right cord or adapter

A 30 A dryer cord for a 3-wire 10-30R will not fit a 4-wire 14-30R; the charts show the different neutral blades before you order.

EV charging

Plug-in Level 2 chargers use a 14-50 or 6-50: on a 50 A circuit they are set to 40 A continuous, 9,600 W at 240 V.

RV shore power

TT-30 is 120 V at 30 A (3,600 W); the 50 A service is a 14-50 with two 120 V legs (2 × 120 V × 50 A = 12,000 W).

Generators and transfer switches

An L14-30 generator outlet carries 120/240 V at 30 A, 240 × 30 = 7,200 W, through a 4-wire cord to a manual transfer switch.

Workshop and welding

A welder with a 6-50P needs a 250 V, 50 A 6-50R receptacle, 2-pole 3-wire with no neutral.