Voltage Unbalance Calculator
Calculate the NEMA percent voltage unbalance of a three-phase supply from its three line-to-line voltages, and see how much a motor on it should be derated.
How to Use
- Measure the three line-to-line voltages (A–B, B–C, C–A) at the motor terminals with a true-RMS meter.
- Enter them; the calculator finds the average.
- It takes the largest deviation of any one voltage from that average.
- Unbalance = 100 × largest deviation ÷ average. Compare it with NEMA's 1% guideline and the derating curve.
Worked Example
A 480 V motor's terminals read 480 V, 475 V and 470 V line to line. The average is (480 + 475 + 470) ÷ 3 = 475 V. The largest deviation is 5 V (480 and 470 both differ by 5), so unbalance = 100 × 5 ÷ 475 = 1.05%, just over NEMA's 1% guideline.
What it does to the motor: current unbalance is typically 6–10 times the voltage figure, so 6–10% here. At 1.96% (460/467/450 V) the motor should be derated to about 95% of its rating.
The common mistake: dividing the spread by the average. (480 − 470) ÷ 475 = 2.1% doubles the answer. NEMA uses the largest deviation from the average, not the difference between the highest and lowest readings.
Show Work
Formulas and NEMA MG 1 Limits
History of Voltage Unbalance Standards
Charles LeGeyt Fortescue's 1918 paper "Method of Symmetrical Coordinates" at the AIEE conference gave engineers a way to decompose any unbalanced three-phase system into three balanced components: positive, negative, and zero sequence. The negative-sequence current created by voltage unbalance spins backwards through induction motors, generating opposing torque, extra heating, and harmonic flux — the reason NEMA limits unbalance to 1%.
NEMA MG 1 (Motors and Generators) gives the derating curve still used today: above 1% unbalance a motor's output should be reduced, to roughly 95% of rating at 2%, 88% at 3%, 82% at 4% and 75% at 5%. Operation above 5% unbalance is not recommended. Current unbalance is typically 6–10× the voltage unbalance because motor impedance to negative-sequence current is much smaller than to positive sequence.
Common causes of field unbalance: single-phase loads unevenly distributed across phases (especially lighting and office receptacles), open delta transformer connections, blown fuses on PFC capacitor banks (removes vars from one phase), and high-impedance connections like corroded lugs. A handheld power quality meter at the motor terminals is the fastest diagnostic.
About This Calculator
Enter the three line-to-line voltages measured at the motor terminals. The tool computes V_avg = (V_AB + V_BC + V_CA)/3, maximum deviation from average, and %VU = 100 × max_deviation / V_avg — the NEMA definition. The readout also shows the recommended motor derate based on NEMA MG-1 curve.
If your %VU exceeds 1%, check for loose connections, imbalanced single-phase loads on the same panel, failed PFC capacitors, or transformer tap imbalance. Measuring current unbalance on the motor leads often reveals 6–10× the voltage unbalance — enough to double insulation temperature rise. Everything runs client-side; no values leave your browser.
Frequently Asked Questions
What limit does NEMA recommend?
NEMA MG 1 says motors should run on supplies with no more than 1% voltage unbalance; above that the motor should be derated, and above 5% operation is not recommended.
How much should a motor be derated?
Roughly to 95% of rated output at 2% unbalance, 88% at 3%, 82% at 4% and 75% at 5%, following the NEMA MG 1 curve.
Why does a small voltage unbalance matter so much?
Unbalanced voltage produces a negative-sequence component that tries to spin the motor backwards. The motor's impedance to it is low, so current unbalance is typically 6–10 times the voltage unbalance, and the extra current heats the windings.
Line-to-line or line-to-neutral voltages?
The NEMA definition uses line-to-line voltages, the ones the motor actually sees. Using line-to-neutral readings can give a different answer on a supply with neutral problems.
What causes unbalance?
Single-phase loads spread unevenly across the phases, a blown fuse in a power-factor capacitor bank, open-delta transformers, and loose or corroded connections on one phase.
How do I use the Voltage Unbalance Calculator?
Simply type your numbers and read the result, which refreshes the instant you change something. There is nothing to submit and nothing to wait for.
Do I need to install or sign up for anything?
Not at all — it runs in the browser with nothing to install and no account. After it loads once, it even works without an internet connection.
Is my information private?
Yes. Everything happens in your browser. Nothing you type is sent to a server or saved anywhere.
Common Use Cases
Motor Commissioning
Measure the supply at a new motor's terminals before running it; anything over 1% should be investigated and the motor derated if it cannot be fixed.
Troubleshooting Hot Motors
A motor running hot at normal load may be suffering from supply unbalance; a few volts' difference between phases can be the cause.
VFD Inputs
A drive's input rectifier draws more current from the higher phases when the supply is unbalanced, increasing DC-bus ripple and stressing the input stage.
Facility Load Balancing
Checking unbalance across a building shows when single-phase loads should be moved to other phases.
Last updated: